62-11389 514
Table 52 Microprocessor Configurations - Continued
Configuration Selections Description
VOLTAGE FOR S/S RESTART
12.2V
12.0 TO 12.8V
The engine will restart from a Start-Stop Off cycle
or a Sleep Mode Off cycle when the battery drops
to this value.
A lower selection may result in a longer off cycle
(based on battery voltage) and possibly overall
shorter battery life. A higher selection may result in
a shorter off cycle (based on battery voltage) and
possibly overall longer battery life.
ENG TEMP FOR S/S RESTART
105F (-12.25C)
10°F to 32°F
(-12.2°C to 0°C)
The engine will restart from a Start-Stop Off cycle
or a Sleep Mode Off cycle when the engine coolant
temperature drops to this value.
ALTERNATOR CHECK
SHUTDOWN:
YES / NO YES = When the A51 - “ALTERNATOR NOT
CHARGING” alarm is activated the alarm light will
illuminate and the unit will shutdown.
NO = When the A51 - “ALTERNATOR NOT CHAR-
GING” alarm is activated the alarm light will illumin-
ate and the unit will continue to run.
BATT CHARGER
(Applicable to unit - not lift gate -
battery charger only.)
NO TEMP
SENSOR
WITH TEMP
SENSOR
NO TEMP SENSOR = Use this setting when the
battery charger does not have the temperature
sensor wire.
WITH TEMP SENSOR = Use this setting when the
battery charger does have the temperature sensor
wire (connected to the battery positive post).
ENGINE OIL LEVEL SWITCH YES / NO YES = An Engine Oil Level switch is installed.
NO = An Engine Oil Level switch is not installed.
ENGINE OIL LEVEL SHUTDOWN YES / NO YES = When the A2 - “LOW ENGINE OIL LEVEL”
alarm is activated the alarm light will illuminate and
the unit will shutdown.
NO = When the A2 - “LOW ENGINE OIL LEVEL”
alarm is activated the alarm light will illuminate and
the unit will continue to run.
LOW COOLANT LEVEL YES / NO YES = A Coolant Level Sensor is installed.
NO = A Coolant Level Sensor is not installed..
ENGINE OIL PRESS SHUTDOWN
YES / NO YES = When the A11 - “LOW ENGINE OIL PRES-
SURE“ alarm has been activated three times in the
last two hours of engine operation the A21 _
“TECHNICIAN RESET REQUIRED“ alarm will be
activated.
NO = A21 will not be activated.
HIGH ENGINE TEMP SHUTDOWN
YES / NO YES = When the A12 - “HIGH COOLANT TEM-
PERATURE” alarm has been activated three times
in the last two hours of engine operation the A21 -
“TECHNICIAN RESET REQUIRED“ alarm will be
activated.
NO = A21 will not be activated.