Carrier VECTOR 6500 - Figure 4−2 Continuous Operation Switch Points with Eco Mode Set to

Carrier VECTOR 6500
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62-11389 46
When Null Mode is required and the system is operating
in:
Engine Operation, the compressor will shutdown
while the engine, condenser fan and evaporator fan
will continue to operate.
Standby Operation, the compressor will shutdown
while the evaporator fan will continue to operate.
FALLING
REFRIGERATED
COMPARTMENT
TEMPERATURE
SWITCH POINT
+0.4F (+0.2C)
Low Speed
2 Cylinder COOL
+1.8F (+1.0C )
+3.6F ( +2.0C )
-3.2F (-1.8C )
Low Speed
4 Cylinder COOL
RISING
REFRIGERATED
COMPARTMENT
TEMPERATURE
SWITCH POINT
+0.9F (+0.5C )
Set point
-0.4_F (-0.2_C)
+1.6F (+0.9C )
+3.2F (+1.8C )
-3.6F (-2.0C )
Pulldown = High Speed
6 Cylinder COOL*
Low Speed
6 Cylinder
COOL
Set point
Low Speed HEAT
HTCON1
+1.1F (+0.6C )
NULL
-0.5F (-0.3C)
-0.4F (-0.2C)
Switch Point = Controlling Temperature - Set Point
+ results are above set point, - results are below set point
Switch points are the same for Perishable Range and Frozen Range except
in Frozen Range heating is not allowed.
* If the HIGH SPEED PULLDOWN Configuration is set to YES, transition
from pulldown is delayed from the indicated +3.2F (+1.8C ) transition
temperature until the temperature is +0.36 F (+0.2C) above set point.
Pull-Up = HEAT
HTCON1 & HTCON2
Figure 42 Continuous Operation Switch Points with Eco Mode set to NO