62-11389
3−3
3. Place the switch labeled START / RUN -
OFF in the START/RUN position.
2. Ensure the external power circuit breaker is off,
connect standby cable to unit and then turn the ex-
ternal power circuit breaker on.
1. Ensure the switch labeled ENGINE/STANDBY
is in the STANDBY position and the switch
labeled START/RUN-OFF is in the OFF posi-
tion
4. The unit will then perform a Self Test (refer to
section 3.3) and start the unit automatically.
START/RUN
OFF
0
I
START/RUN
OFF
STANDBY
ENGINE
I
O
Starting units with a Main Power switch labeled START/RUN-OFF.
+34.5 F
-20.0
NOTE
The unit is equipped with automatic phase re-
versal which ensures that the electric motors
will run in the correct direction.
For safe, reliable operation in Standby Operation, it
is important to consider the following guidelines:
• NEVER connect the unit to a high voltage power
source unless the Main Power Switch is in the OFF
position.
• The power supply cable and circuit breaker must
comply with local electrical code and unit specifica-
tions. Refer to section 2.11.
• The power supply cable must be equipped with a
ground connection.
• Repairs or maintenance to the supply voltage circuit
should only be performed by licensed / authorized
personnel.