EasyManua.ls Logo

Carrier VECTOR 6500 - HARNESS PLUG WIRING FOR UNITS WITH A MAIN POWER SWITCH LABELED START;RUN-OFF

Carrier VECTOR 6500
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10662-11389
10.2 HARNESS PLUG WIRING FOR UNITS WITH A MAIN POWER SWITCH LABELED START/RUN-OFF
1MP - NATURAL
1
12
24
35
Component Terminal
REMSN1 (REMSN-E) 3 (14)
REMSN2 (REMSN-H) 4 (14)
CDP-C 5 (16) (30)
EVOP-C (DP16-S) 6 (17) (30)
ENCT 7 (18)
CDT 9 (20)
CST 10 (19)
AAT 11 (22)
1RAT (DP16-G) 12 (23)
REMSN1 (REMSN-F) (SP1) 14 (3)
REMSN2 (REMSN-G) (SP1) 14 (33)
REMSN3 (REMSN-K) (SP1) 14 (33)
1MP - NATURAL (Continued)
Component Terminal
CSP-A (SP16) 15 (29) (30)
OGF-OV (HC-1) (SP16) 15
CDP-A 16 (5) (30)
EVOP-A (DP16-P) 17 (6) (30)
ENCT 18 (7)
CST (SP14) 19 (10)
EVOT (DP16-F) (SP14) 19 (32)
CDT 20 (9)
DTT (DP16-B) 21 (34)
AAT 22 (11)
1SAT (DP16-D) (SP12) 23 (35)
1RAT (DP16-H) (SP12) 23
FLS-C 26
CSP-C 29 (15) (30)
CSP-B (SP7) 30 (15) (29)
CDP-B (SP7) 30 (5) (16)
EVOP-B (SP7) (DP16-R) 30 (6) (17)
EVOT (DP16-E) 32 (19)
REMSN3 (REMSN-J) 33 (14)
2RAT (2EVC-J) 33 (23)
DTT (DP16-A) 34 (21)
1SAT (DP16-C) 35 (23)
Unused terminals: 1, 2,8,13,21, 24, 25, 27,28,31