Carrier VECTOR 6500 - Figure 4−3 Continuous Operation Switch Points with Eco Mode Set to YES

Carrier VECTOR 6500
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62-1138947
FALLING
REFRIGERATED
COMPARTMENT
TEMPERATURE
SWITCH POINTS
-3.2F (-1.8C )
RISING
REFRIGERATED
COMPARTMENT
TEMPERATURE
SWITCH POINTS
Set point
-3.6F (-2.0C )
Pulldown = High Speed
6 Cylinder COOL
Low Speed
6 Cylinder
COOL
Set point
Low Speed HEAT
HTCON1
NULL
-1.4F (-0.8C)
-1.3F (-0.7C)
Switch Point = Controlling Temperature - Set Point
+ results are above set point, - results are below set point
Switch points are the same for Perishable Range and Frozen Range except
in Frozen Range heating is not allowed.
Enter cool at Start-Stop
Override Functional
Parameter Value
(+3.6 to 185F = +2 to 105C)
Enter high speed at
Start-Stop Override Func-
tional
Parameter Value + 2
(+7.2 to 23.45F = +4 to 125C)
Transition to low speed at
Start-Stop Override
Functional Parameter
Value + 1
(+5.4 to 19.85F = +3 to 115C)
Pull-Up = HEAT
HTCON1 & HTCON2
Figure 43 Continuous Operation Switch Points with Eco Mode set to YES