Table 52 Microprocessor Configurations - Continued
 PRODUCTSHIELD ECONO
MIN TEMP
OFF or
-20°F to +119.0°F
(-28.9°C to
+48.4°C )
(in 0.5° incre-
ments)
Default: 119.0°F
(48.4°C )
OFF = There is no lower limit for this parameter.
Select the lowest ambient temperature desired to
activate ProductShield Econo.
If ProductShield Econo is Go To Continuous there
is a minimum 10°F range. Therefore, this parame-
ters upper limit is ProductShield Econo Maximum
Temperature minus 10°F (5.5°C).
 PRODUCTSHIELD ECONO
MAX TEMP
OFF or
-20°F to +119.0°F
(-28.9°C to
+48.4°C )
(in 0.5° incre-
ments)
Default: 119.0°F
(48.4°C)
OFF = There is no upper limit for this parameter.
Select the highest ambient temperature desired to
activate ProductShield Econo
If ProductShield Econo Install is Go To Continuous
there is a minimum 10°F range. Therefore, this pa-
rameters lower limit is ProductShield Econo Min
Temp plus 10°F (5.5°C).
 PRODUCTSHIELD
ECONO - DELTA-T
(used for “Go To S/S” only, not
available for “Go To Cont”)
OFF
+3.6°F to +27.0°F
(+2°C to 15°C) (in
0.5° increments
OFF = Delta-T is not used in determining when the
unit will go into Econo: Go To Start/Stop mode.
Select the desired delta-T value for activation of
ProductShield Econo. When Delta-T is below this
setting and within the minimum/maximum range, go
to start/stop will be allowed
PRODUCTSHIELD HIGH AIR
OFF OFF = The unit will operate normally in high and
low speeds.
ON ON = The unit will operate in high speed when the
ambient air temperature is outside a user defined
range. This provides increased air flow and good
product protection for extreme ambient temperat-
ures. Unit may return to low speed when ambient
comes back within the range.
 HIGH AIR MIN. TEMP
OFF
OFF = There is no lower limit for this parameter.
-19°F to +119°F
(-28.3°C to
+48.3°C )
in 0.5°F or °C
increments
Default: 119°F
(48.3°C )
Select the lower limit of the ambient range desired
for this parameter. Refer to Section 4.7.3 for more
information on High Air Min. Temp.
 HIGH AIR MAX. TEMP
OFF OFF = There is no upper limit for this parameter.
-19°F to +119°F
(-28.3°C to
+48.3°C )
in 0.5°F or °C
increments
Default: 119°F
(48.3°C )
Select the upper limit of the ambient range desired
for this parameter. Refer to Section 4.7.3 for more
information on High Air Max. Temp.
 HIGH AIR DELTA-T
OFF OFF = Delta-T is not used for determining the activ-
ation/de-activation of High Air Delta-T
+3.6° F to +27.0°F
(+2°C to 15°C)
in 0.5° C or °F in-
crements
Select the desired Delta-T value for activation of
ProductShield High Air. Refer to Section 4.7.3 for
more information on High Air Delta-T.
PRODUCTSHIELD WINTER - XX° OFF
-20°F to +32.0°F
(-28.9°C to 0°C) (in
0.5° C or °F incre-
ments
Select the desired ambient temperature below
which ProductShield Winter will operate (forced
Continuous Run operation.)