62-11389
799
Alarm
NO.
Steps Alarm/Cause Corrective Action
225 GENERAL MAINTENANCE DUE
TRIGGER–ON: The General Maintenance Hour Meter time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1 Check Unit Maintenance Records
Schedule unit into service facility for
maintenance.
Must be done soon!
2 Perform Maintenance
Perform appropriate engine & unit
maintenance.
Follow instructions on proper maintenance form.
3 Reset General Maintenance Hour Meter
a. Check that the General
Maintenance Hour Meter interval is
set for your requirements.
Reset configured Interval if required.
b. Reset General Maintenance Hour
Meter for the next service interval.
Hour Meter reset is a Functional Parameter.
Follow maintenance interval recommendations in
Section 8.2.
226 SERVICE SOON-PM #1 DUE
TRIGGER–ON: The Maintenance Hour Meter #1 time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1 Check Unit Maintenance Records
Schedule unit into service facility for
maintenance.
Must be done soon!
2 Perform Maintenance
Perform appropriate engine & unit
maintenance.
Follow instructions on proper maintenance form.
3 Reset Maintenance Hour Meter #1
a. Check that Maintenance Hour
Meter #1 interval is set for your
requirements.
Reset configured Interval if required.
b. Reset Maintenance Hour Meter #1
for the next service interval.
Hour Meter reset is a Functional Parameter.
Follow maintenance interval recommendations in
Section 8.2.