EasyManua.ls Logo

Cattron Safe-E-Stop - Dual-Channel Connection Example Using E-Stop Relays and the COMM LOSS Relays

Cattron Safe-E-Stop
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
Version 17
Safe-E-Stop™
User Guide
8.2.4 Dual-Channel Connection Example using E-Stop relays and the COMM LOSS relays
The following configuration combines the SIL3 function of the COMM LOSS relays with the systematic capability
of 3 provided by the E-Stop relays in a dual channel configuration.
The Ethernet bus may be used to give visual feedback of PSD status or total number of PSDs linked, or to allow
the green button to light a lamp, etc. This makes it possible to run the machine with the hard-wired E-Stop switch
in use and no PSD in use.
The dual-channel connection method below ensures a high level of reliability and monitoring is imposed; provided
the safety PLC inputs are OR’d, no single-channel wiring fault will be possible.
Additionally, if the machine is to be run without a PSD connected at times, this will not be possible without either
overriding or not using the COMM LOSS relays, because their state will be open without a PSD linked.
The COMM LOSS reset function is not shown but is still required, see Fig 12.
Figure 15: MSD Typical Dual Channel Connections When Using the COMM LOSS Relays
The COMM LOSS reset function is not shown but is still required, see Fig 12.

Table of Contents