EasyManua.ls Logo

Chamberlain SL600 - SETTINGS; Gate Operation Parameters

Chamberlain SL600
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
Increased Starting Force
When activated, the operator will run with higher
force for fi rst 2+/-1 seconds than the normal
running force.
1 ON = Higher starting force
1 OFF = Standard starting force
Partial Open Setting
When on, the partial open setting will open the
gate 1 meter. Refer to the Programming section for
instructions to program the remote control for this
setting.
2 ON = Partial Open ON
2 OFF = Partial Open OFF
Auto Closing Setting
Switches shall be used to set timer to close
duration from 0-105 seconds by adding the values
of each switch in the ON position. Each switch
value shall be the following:
6 ON = 15 seconds
7 ON = 30 seconds
8 ON = 60 seconds
Limit Switch Setting
Factory default is set to OFF (normal open).
4 ON = Travel limit switch is set to
normal close
4 OFF = Travel limit switch is set to
normal open
1 2 3 4 5 6 7 8
S1
ON
OFF
Increased Starting Force is on
SETTINGS
1 2 3 4 5 6 7 8
S1
ON
OFF
Partial Open is on
1 2 3 4 5 6 7 8
S1
30 Seconds
ON
OFF
1 2 3 4 5 6 7 8
S1
Normal open
ON
OFF

Table of Contents

Related product manuals