FAULT #33 - Internal PLC error. PWM Pulses not seen on input
#6. – [Check the wiring to input #6 or 24VDC power.]
FAULT #34 - Internal PLC error. PWM Pulses not seen on input
#8. – [Check the wiring to input #8 or 24VDC power.]
FAULT #35 - Internal PLC error. PWM Pulses not seen on input
#10. – [Check the wiring to input #10 or 24VDC power.]
Level 5 Alarms – These alarms disable dosing. These alarms trigger a solid red light.
FAULT #50 - Estop PB not seen on input #14. – [The red
mushroom pushbutton on the front of the Doser control panel is
pushed.]
FAULT #51 - Remote Disable on. – [The remote Doser disable is
active.]
FAULT #53 - Bottle Sensor Pulses seen too fast. – [Check the
encoder. Too many pulses were detected than are allocated
between timing sensor signals.]
Alarm History
The alarm screen automatically clears itself of fault conditions once the fault itself has been cleared. The
Alarm History screen is similar to the Alarm screen but keeps a total history of all fault conditions. The
alarm log does not automatically clear the faults so these conditions are kept until manually cleared by the
administrator.