Chloride Active
UK
GENERAL
Bypass
Yes (automatic)
Effi ciency in line
mode (%)
86% 86% 86%
88% 90%
Maximum Acoustic
Noise in on-line
mode at 1 meter
(dB)
40
41 41 47 47
Variable fan speed
Yes
External battery
packs
No
Yes
Color
Grey Anthracite (RAL7016)
CONNECTIVITY
Communication
Ports
1xDB9 (RS232 signals and status signals), 1xUSB (***)
Communication
Slot
1xslot for SNMP/TCP-IP/Web interface or volt-free contacts card accessory
Remote Power Off
(RPO)
Yes
Remote On/Off
(ROO)
Yes
Status signals
Opto-coupled, open-collector signals available at DB9 port: Battery Low, AC Fail, Bypass Active,
SUM Alarm
ENVIRONMENTAL
Operating
temperature
0 - 40 ºC
Storage
temperature
-25 ºC / +50 ºC without batteries, -15ºC / +40ºC with batteries
Altitude 0-3000m
Relative humidity 10% to 90%
CONNECTIONS
Input
1 x IEC320 C14 (10A)
1 x IEC320
C20 (16A)
Output 6 x IEC320 C13 (10A), 3 of them controllable (2 groups)
6 x IEC320
C13 (10A),
3 of them
controllable
(2 groups)
1 x IEC320
C19 (16A)
NORMATIVES
CE Mark Yes
Safety EN 62040-1, EN 60950 (RD), TÜV, CB report, UL/cUL
EMC IEC62040-2, class C2; IEC61000-4-3/3/4/5/6/8/11; VDE160; IEC61000-2-2
Performance EN62040-3
(*)Output power with external battery packs is – 1000VA models: 1000VA/800W, 1500VA models:
1500VA/1200W, 2000VA models: 2000VA/1600W, 3000VA models: 3000VA/2400W.
(**) For output nominal voltage 200V, there is a power de-rating of 20% (the unit’s nominal power is
reduced by 20%). For output nominal voltage 208V, there is a power de-rating of 10% (the unit’s nominal
power is reduced by 10%).
(***) Both ports cannot be used simultaneously.