40
UK
Chloride Active
945044.066
8.1.2 Battery Packs
BP-A1000/1500-T BP-A1000/1500-RT BP-A2000/3000-RT
Housing
Tow er
Rack/Tower Rack/Tower
Battery arrangement
2x3x7,2Ah
2x3x7,2Ah 2x6x9Ah
Protection
Breaker 70A/80Vdc
Breaker 70A/80Vdc Breaker 70A/80Vdc
MECHANICAL
Size (WxHxD, mm)
157x245x438
438x86(2U)x438 438x86(2U)x657
Weight (kg)
20
32 52
ENVIRONMENTAL
Operating temperature 0 - 40 ºC
Storage temperature -15 ºC / +40 ºC
Altitude 0-3000m
Relative humidity 10% to 90%
8.2 Runtime charts
Theoretical values with fully charged batteries and resistive load.
NOTE: The maximum quantity of external battery packs that can be connected to the UPS is four.
Active 700 T:
Load UPS
UPS
+ 1 BP
UPS
+ 2 BP
UPS
+ 3 BP
UPS
+ 4 BP
80W 63 min 239 min 438 min 661 min 861 min
160W 37 min 158 min 254 min 397 min 476 min
240W 26 min 91 min 197 min 262 min 372 min
320W 20 min 69 min 145 min 212 min 263 min
400W 15 min 55 min 97 min 174 min 220 min
480W 13 min 45 min 80 min 136 min 191 min
560W 11 min 38 min 69 min 99 min 161 min
640W
9 min 33 min 60 min 86 min 130 min
720W 7 min 29 min 51 min 75 min 99 min
800W 6 min 25 min 46 min 67 min 89 min
Active 1000 T and Active 1000 RT:
Load UPS
55W 51 min.
110W 35 min.
170W 24 min.
225W 18 min.
280W 15 min.
335W 12 min.
390W 10 min.
450W 8 min.
505W 7 min.
560W 5 min.