3.7 Floor Loading
Taking into consideration the weight of the UPS and extension battery packs of Tower models and RT
models operating as Tower, it is necessary that the fl oor in the chosen location be capable of supporting the
weight of the units.
NOTE: Weights for the UPS and battery packs are shown in section 8 (“Technical Specifi cations”).
3.8 Rack Loading
Taking into consideration the weight of the UPS and extension battery packs of RT models that may be
mounted in an associated rack, it is necessary that the chosen cabinet be capable of supporting the weight
of the units.
NOTE: Weights for the UPS and battery packs are shown in section 8 (“Technical Specifi cations”).
3.9 Ventilation
It is necessary to leave a minimum space of at least 50 mm in front and rear of the UPS to allow a fl ow of
air.
Electrical maintenance and servicing requires access to the front and back of the UPS. Provide the
necessary space to allow service personnel access to the UPS.
3.10 Installation Data
3.11 Rack-Mounting the UPS or External Battery Cabinets (RT Models Only)
The Rack/Tower UPS’s and external battery packs can be rack-mounted in four-post frames. The UPS and
external battery packs use identical mounting hardware and the procedure for mounting either is the same.
ATTENTION: The UPS draws cooling air from the front. If the rack has a door on the front, make sure that
there is some clearance between the vents and the rack door.
Because of the weight and dimensions of these units (particularly the 2 and 3kVA models), it is strongly
recommended that two people lift the unit for rack-mounting. If only one person is available, it may be
possible to disconnect and take out the UPS internal batteries, rack-mount the UPS without batteries (less
weight) and re-connect the internal batteries once that the UPS is rack-mounted.
Item Specifi cation
Ambient temperature 0ºC to 40ºC
Relative humidity (non condensing) 20%-90%
Environment Controlled (offi ce or similar)
Max. altitude (w/o derating) 3.000 meters
Input power connection Rear
Output power connection Rear
Battery power connection Rear
Air inlet Front
Air outlet Rear