38
UK
Chloride Active
945044.066
8 Specifi cation and back-up times
8.1 Specifi cation
NOTE: We reserve the right to modify the information in these tables without prior notice.
8.1.1 Uninterruptible Power Supplies
Active
700 T
Active
1000 T
Active
1000 RT
Active
1500 T
Active
1500 RT
Active
2000 RT
Active
3000 RT
UPS Rating 700VA 1000VA 1500VA 2000VA 3000VA
Housing Tower Tower Rack/Tower Tower
Rack/Tower Rack/Tower Rack/Tower
Technology Advanced on-line double conversion
Output Power
(VA/W)
700/630
1000/900(*) 1500/1350(*)
2000/1800(*)
3000/2700(*)
INPUT
Nominal input
voltage (VAC)
200-240V
Operative input
voltage range (VAC)
120V-284V (depending on output load)
140-284V (depending on
output load)
Nominal input
frequency (Hz)
50/60Hz auto-selection
Operative input
frequency range
(Hz)
50/60Hz +/-5% (40/70Hz if Frequency Converter Mode is activated)
Input power factor 0,99 (batteries charged)
OUTPUT
Waveform
Pure sinusoidal
Nominal output
voltage (VAC)
200(**) / 208(**) / 220 / 230(default) / 240 V (confi gurable via user software and optional LCD
Display) (250 V under request)
Voltage regulation
(%)
3%
Output frequency
(Hz)
50/60Hz ±0,5% (same as input or selectable in Frequency Converter Mode)
Harmonic distortion
(linear/non-linear
load) THDv
Max. 4% / Max. 8%
Transfer time (line-
battery-line) (s)
0
Overload capacity
(line mode, output
power factor 0.9)
<110% warning // 111-130%: 12 seconds (UPS to bypass) // >130%: 1,5 seconds (UPS off)
Shortcircuit
protection
Yes
BATTERIES
Type
Sealed maintenance-free lead acid (VRLA)
Arrangement
1x2x7,2Ah
1x3x7,2Ah 1x3x9Ah
1x6x7,2Ah 1x6x9Ah
Advanced Battery
Care
Yes
Battery
management
Battery pack auto detection, automatic runtime calculation, protection against deep discharge
MECHANICAL
Size (WxHxD, mm)
157x245x438 157x245x438
438x86
(2U)x482
157x245x488
438x86
(2U)x482
438x86
(2U)x657
438x86
(2U)x657
Weight (kg) 13 15 18 18
20
26 31