8.3 Information available while the unit is running
In the [2 - Machine status] menu: menu displayed on the screen if the control console is not used for one hour.
Default Information
No faults Setpoint and measurement values displayed.
Sensor fault The fault LED flashes and a message states which loop has a fault
Fan fault The fault LED flashes and a message states which stage has a fault
In the [3 - Measured values] menu:
Parameter Description Display conditions
Outdoor temperature Value displayed Misting
Coil pressure Value displayed 1 refrig. circuit
Pressure, circuit or coil 1 Value displayed 2 refrig. circuit
Pressure, circuit or coil 2 Value displayed 2 refrig. circuit
In the [6-Reading parameters] menu:
Parameter No. Description Display conditions
A250 LED test: press Enter to check the operation of the LEDs
A252 Outdoor air temperature Misting
A253 Value of circuit or coil 1 setpoint
A254 Value of circuit 2 setpoint 2 refrig. circuits + flatbed unit
A255 Value of coil 2 setpoint V-type unit
A258 Value of circuit or coil 1 pressure
A260 Value of circuit 2 pressure 2 refrig. circuits + flatbed unit
A262 Value of coil 2 pressure V-type unit
A270 to A276 Running time of each stage 1 refrig. circuit or 1 fan line
A280 to A295 Running time of each stage on each line 2 refrigerant circuits + 2 fan lines
A299 Misting time Misting
A316 Terminal block J9 connection From V09
A400 to A421 Status (open or closed) of the logic inputs on the board
A430 to A451 Status (open or closed) of the logic outputs on the board
A460
If 1 refrigerant circuit = Fan speed in %
If 2 refrigerant circuits and 2 fan lines = Line 1 fan speeds
Control = mixed or speed control
A461 Speed (in%) of fans on line 2
Control = mixed or speed control + 2 refrig. circuits +
2 fan lines
From V07
A470 Supply voltage Energy meter
A471 Machine input current Energy meter
A472 Machine power input energy meter
A473 Electrical energy consumed Energy meter
A555 CPU board version No.
A556 Control console version No.
A557 Daughter board version No.
In the [7-Default memory] menu:
Record of the nine most recent faults on the fan stages or pressure sensors, or the outdoor temperature sensor.
To scroll through the faults, press