9.7 Counters (read-only)
Registers 300 and 301: Fan runtime, stage 1, line 1
Registers 302 and 303: Fan runtime, stage 2, line 1
Registers 304 and 305: Fan runtime, stage 3, line 1
Registers 306 and 307: Fan runtime, stage 4, line 1
Registers 308 and 309: Fan runtime, stage 5, line 1
Registers 310 and 311: Fan runtime, stage 6, line 1
Registers 312 and 313: Fan runtime, stage 1, line 2
Registers 314 and 315: Fan runtime, stage 2, line 2
Registers 316 and 317: Fan runtime, stage 3, line 2
Registers 318 and 319: Fan runtime, stage 4, line 2
Registers 320 and 321: Fan runtime, stage 5, line 2
Registers 322 and 323: Fan runtime, stage 6, line 2
Registers 324 to 398: Spare
9.8 Remote configuration register (read and write)
Register 399: Unit type (A01) 0 flat type, 1 V type
Register 400: If A01 = type V: A02 parallel coil 0 = NO, 1 = YES
If A01 = flat A02 number of coils
Register 401: Coil 1 type (A03)
0 1 low-temperature water circuit
1 2 low-temperature water circuits
2 1 high-temperature water circuit
3 2 high-temperature water circuits
4 1 refrigerant circuit
5 2 refrigerant circuits
Register 402: A04: Circuit type, coil 1
0 balanced circuit
1 unbalanced circuit
Register 403: A05: Coil 2 type
0 1 low-temperature water circuit
1 2 low-temperature water circuits
2 1 high-temperature water circuit
3 2 high-temperature water circuits
4 1 refrigerant circuit
5 2 refrigerant circuits
Register 404: A06: Circuit type, coil 2
0 Balanced circuit
1 Unbalanced circuit
Register 405: A07: Control type
0 On/Off
1 Variable speed control
2 Mixed energy
Register 406: A08: Number of fan stages
Register 407: A09 :Number of fan lines
Register 408: A10: Misting (0 = NO, 1 = YES)
Registers 409 and 410: A30: HP sensor high value coil 1 circuit 1
Registers 411 and 412: A31: HP sensor low value coil 1 circuit 1
Registers 413 and 414: A32: HP sensor high value coil 1 circuit 2
Registers 415 and 416: A33: HP sensor low value coil 1 circuit 2
Registers 417 and 418: A34: HP sensor high value coil 2 circuit 1
Registers 419 and 420: A35: HP sensor low value coil 2 circuit 1
Registers 421 and 422: A36: HP sensor high value coil 2 circuit 2
Registers 423 and 424: A37: HP sensor low value coil 2 circuit 2
Register 425: A99: Locking
0 : NO
1 : YES
Register 426: A15.1 Presence of energy management module
0 NO
1 YES
Register 427: A15.2 Type of network
0 1BL - 1 2BL - 2 3BL - 3 3NBL
4 4BL - 5 4NBL
Register 428: A16 Primary current transformer rating
Register 450: A110: Optimised fan operation
0 NO
1 YES
Register 451: A120: Number of setpoints
0 1 setpoint
1 2 setpoints via CMS system or console
2 2 setpoints per On/Off input