EN7510364-00
EN - 30
Registers 452 and 453: A121: Setpoint 1, coil 1, circuit 1
Registers 454 and 455: A122: Setpoint 2, coil 1, circuit 1
Registers 456 and 457: A123: Setpoint 1, coil 1, circuit 2
Registers 458 and 459: A124: Setpoint 2, coil 1, circuit 2
Registers 460 and 461: A125: Setpoint 1, coil 2, circuit 1
Registers 462 and 463: A126: Setpoint 2, coil 2, circuit 1
Registers 464 and 465: A127: Setpoint 1, coil 2, circuit 2
Registers 466 and 467: A128: Setpoint 2, coil 2, circuit 2
Registers 468 and 469: A150: Hysteresis stage 1 battery 1, circuit 1
Registers 470 and 471: A151: Setpoint 2, coil 1, circuit 1
Registers 472 and 473: A152: Hysteresis stage 2, coil 1, circuit 1
Registers 474 and 475: A153: Setpoint difference stage 3, coil 1, circuit 1
Registers 476 and 477: A154: Hysteresis, stage 3, coil 1, circuit 1
Registers 478 and 479: A155: Setpoint difference, stage 4, coil 1, circuit 1
Registers 480 and 481: A156: Hysteresis stage 4, coil 1, circuit 1
Registers 482 and 483: A157: Setpoint difference stage 5, coil 1, circuit 1
Registers 484 and 485: A158: Hysteresis stage 5, coil 1, circuit 1
Registers 486 and 487: A159: Setpoint difference stage 6, coil 1, circuit 1
Registers 488 and 489: A160: Hysteresis stage 6, coil 1, circuit 1
Registers 490 and 491: A161: Hysteresis stage 1, coil 1, circuit 2
Registers 492 and 493: A162: Setpoint difference stage 2, coil 1, circuit 2
Registers 494 and 495: A163: Hysteresis stage 2, coil 1, circuit 2
Registers 496 and 497: A164: Setpoint difference, stage 3, coil 1, circuit 2
Registers 498 and 499: A165: Hysteresis stage 3, coil 1, circuit 2
Registers 500 and 501: A166: Setpoint difference stage 4, coil 1, circuit 2
Registers 502 and 503: A167: Hysteresis stage 4, coil 1, circuit 2
Registers 504 and 505: A168: Setpoint difference, stage 5, coil 1, circuit 2
Registers 506 and 507: A169: Hysteresis stage 5, coil 1, circuit 2
Registers 508 and 509: A170: Setpoint difference stage 6, coil 1, circuit 2
Registers 510 and 511: A171: Hysteresis stage 6, coil 1, circuit 2
Registers 512 and 513: A172: Hysteresis stage 1, coil 2, circuit 1
Registers 514 and 515: A173: Setpoint difference stage 2, coil 2, circuit 1
Registers 516 and 517: A174: Hysteresis, stage 2, coil 2, circuit 1
Registers 518 and 519: A175: Setpoint difference stage 3, coil 2, circuit 1
Registers 520 and 521: A176: Hysteresis stage 3, coil 2, circuit 1
Registers 522 and 523: A177: Setpoint difference stage 4, coil 2, circuit 1
Registers 524 and 525: A178: Hysteresis stage 4, coil 2, circuit 1
Registers 526 and 527: A179: Setpoint difference stage 5, coil 2, circuit 1
Registers 528 and 529: A180: Hysteresis stage 5, coil 2, circuit 1
Registers 530 and 531: A181: Setpoint difference stage 6, coil 2, circuit 1
Registers 532 and 533: A182: Hysteresis stage 6, coil 2, circuit 1
Registers 534 and 535: A183: Hysteresis stage 1, coil 2, circuit 2
Registers 536 and 537: A184: Setpoint difference, stage 2, coil 2, circuit 2
Registers 538 and 539: A185: Hysteresis stage 2, coil 2, circuit 2
Registers 540 and 541: A186: Setpoint 3 difference, coil 2, circuit 2
Registers 542 and 543: A187: Hysteresis, stage 3, coil 2, circuit 2
Registers 544 and 545: A188: Setpoint difference stage 4, coil 2, circuit 2
Registers 546 and 547: A189: Hysteresis stage 4, coil 2, circuit 2
Registers 548 and 549: A190: Setpoint difference stage 5, coil 2, circuit 2
Registers 550 and 551: A191: Hysteresis stage 5, coil 2, circuit 2
Registers 552 and 553: A192: Setpoint difference, stage 6, coil 2, circuit 2
Registers 554 and 555: A193: Hysteresis stage 6, coil 2, circuit 2
Registers 556 and 557: A197: Temperature value for 0% on the 3-way valve output
Registers 558 and 559: A198: Temperature value for 10% on the 3-way valve output
Register 560: A199: Outdoor temperature for start of misting
Registers 561 and 562: A200: misting difference, coil 1, circuit 1
Registers 563 and 564: A201: misting difference, coil 1, circuit 2
Registers 565 and 566: A202: misting difference, coil 2, circuit 1
Registers 567 and 568: A203: misting difference, coil 2, circuit 2
Register 569: A113: Type of misting (0: water optimisation, 1: electricity optimisation)
Registers 570 and 571: A114: Max. voltage at fan output 0-10 V
Registers 572 and 573: A106: Range without activation
Register 574: A107: Activation delay between each stage
Register 575: A108: Deactivation delay between each stage
Register 576: A119.1: Type of coil 1 fluid
0 Water - 1 Glycol 10% - 2 Glycol 20%
3 Glycol 30% - 4 Glycol 40%
Register 577: A119.2: Type of fluid, coil 2
0 Water - 1 Glycol 10% - 2 Glycol 20%
3 Glycol 30% - 4 Glycol 40%