EasyManua.ls Logo

CIAT Connect 2 - Cascade control; Control in parallel with shifted setpoint

CIAT Connect 2
101 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
88
A) Cascade control:
Note: P804 = Cascade parameter P143 on each machine becomes equal to 1°C. This is because the interstage differential on each
machine will be adjusted by the value of P143 on each machine.
Machine 2s setpoint is shifted by P806 relative to machine 1s setpoint. The value of P806 will have to be selected based on machine 1 in
order to achieve an operating order similar to the start-up of the last stage (see figure above).{
B) Control in parallel with "shifted setpoint":
Machine 1 adjusts itself to the master machines setpoint. Machine 2s setpoint is shifted by the value of P805. Thus, the machine 2s setpoint
2 is machine 1s setpoint + P805.
Machine 1
Stage 1
Machine 2
Stage 2
Machine 1
stage
Machine 2
stage
Machine 1
STP
Machine 2
STP
Master machine
STP

Table of Contents

Related product manuals