Parameters P608 and P618 are visible only if P2 reversible air-to-water
Operation parameters:
23.2.2 Manual EXPANSION VALVE MODE if P42 = CIAT:
If Test Mode is set to Yes it retains all standard testing functionalities and provides access to the manual override menu for the electronic
expansion valves when is pressed.
Manual override of expansion valves (opening and closing)
If P3 = 1, access to EXV TEST.1 mode only.
Press + and to change expansion valves.
Display:
When either test mode is confirmed (OK ), access is to the settings menu is provided.
Display:
The expansion valve remains in automatic mode the entire time AUTO is displayed. To enter settings mode, press OK.
- To send a signal to open the valve, press + The percentage immediately higher than the percentage of opening requested by the
controller will appear.
- To send a signal to close the valve, press The percentage immediately lower than the percentage of opening requested by the
controller will appear.
To adjust the valves percentage of opening to the desired value, press + and . This percentage can be changed in increments of 1%.
P 6 1 2 C I R C U I T 2
S U P E R H E A T S T P 6 ° C
P 6 1 3 C I R C U I T 2
M O P P O I N T Y E S
P 6 1 4 C I R C U I T 2
MOP V A L U E 1 5 ° C
P 6 1 5 O P N G C 2 E X V
S T A R T A I R C O N X X X %
P 6 1 6 O P N G C 2 E X V
S T A R T H E A T P U M P X X X %
P 6 1 7 O P E N I N G T I M E
S T A R T C 2 X X S
P 6 1 8 C I R C U I T 2
S L O W M O D E NO
P 3 2 5 C 1 E X V
O P E N I N G X X X %
P 3 5 5 C 2 E X V
O P E N I N G X X X %
P 5 5 8 C I R 1 E X V V E R S I O N
N O . X X . Y Y V C M X X . Y Y
P 5 5 9 C I R 2 E X V V E R S I O N
N O . X X . Y Y V C M X X . Y Y
E X V T E S T . 1
E X V T E S T . 2
E X V T E S T C X
A U T O