EN - 13
Access
level
No. Description Setting Default Display conditions
OPTION (CONTINUED)
2
28 Master/slave control of two machines Yes/No No
2
29 Total recovery Yes/No No If P2 = 2
Breakdown
3
30 High pressure, HP1 sensor 10 to 50 bar (resolution: 0.1) 34
3
31 Low pressure, HP1 sensor –1 to 10 bar (resolution: 0.1) –0.5
3
32 High pressure, HP2 sensor 10 to 50 bar (resolution: 0.1) 34 If P3 = 2
3
33 Low pressure, HP2 sensor –1 to 10 bar (resolution: 0.1) –0.5 If P3 = 2
3
34 HP3 sensor high value 10 to 50 bar (resolution: 0.1) 34 If P3 = 3
3
35 HP3 sensor low value –1 to 10 bar (resolution: 0.1) –0.5 If P3 = 3
3
36 High pressure, LP1 sensor 10 to 50 bar (resolution: 0.1) 17.3
3
37 Low pressure, LP1 sensor –1 to 10 bar (resolution: 0.1) 0
3
38 High pressure, LP2 sensor 10 to 50 bar (resolution: 0.1) 17.3 If P3 = 2
3
39 Low pressure, LP2 sensor –1 to 10 bar (resolution: 0.1) 0 If P3 = 2
3
40 LP3 sensor high value 10 to 50 bar (resolution: 0.1) 17.3 If P3 = 3
3
41 LP3 sensor low value –1 to 10 bar (resolution: 0.1) 0 If P3 = 3
3
42 Electronic expansion valve Yes/No No
3
43 Superheat protection Yes/No No
3
44 Minimum superheat temperature 0 to 5 K (resolution: 0.1) 0.5 K If P43 = Yes
3
45 Maximum superheat temperature 10 to 20 K (resolution: 0.1) 15.0 K If P43 = Yes
3
48 Valve opening temperature 80 to +6°C (resolution 0.5) 110°C
3
49 Intake closing differential 5 to +6°C (resolution 0.5) 10°C
3
51 Discharge temperature limit 60 to +6°C (resolution 1) 115
3
52 Water line frost protection limit
–25 to +6°C (resolution 0.1)
2
3
54 HP fault threshold 15 to 45 bar (resolution: 0.1) 18 b
3
55 LP fault threshold 0.1 to 5 bar (resolution: 0.1) 0.3 b
3
56 Minimum discharge superheat temperature 0 to 30 seconds (resolution: 1) 10°C
3
57 HPS cut-out HP value 15 to 30 bar (resolution: 0.1) 15.8 b
3
61 Liquid valve opening time 0 to 180 seconds (resolution: 1) 0
3
62 Liquid valve closing time 0 to 180 seconds (resolution: 1) 0
3
70 Control LP limit differential. 0 to 10 K (resolution: 0.5) 8
2
99 Parameter locking No - Yes No
Customer Configuration
2
100 Language F-GB-D-SP-I F
2
101 Date DAy/MOnth/YEar
2
102 Time HOurs/MInutes
1
103 Control mode Local - remote (BMS) Local
2
108 Pump 2 control. Fct (Control) - Fct (On/Off) if P2 = 1 Fct (on/off) If P24 = No
2
116 AEROCONNECT link Yes - No No
1
117 Power input limit
No - At all times - Yes via on/off input - Yes via
bus
No If P15 = Yes
1
118.1 Maximum power threshold 100 to 1000 kW 600 If P15 = Yes
1
118.2 Difference from max. power 5 to 100 kW 50 If P15 = Yes
Setpoint management
1
119 Operating mode
1 - Cooling
2 - Heating
3 - Cooling/heating via console
4 - Cooling/heating via on/off input
5 - Automatic cooling/heating based on
outdoor temperature
Cooling
1
120 Number of setpoints
1 - 2 via console - 2 via on/off input
3 Setpoint managed by 4-20 mA signal
1
1
121 Cooling setpoint 1 P52 + 3 K at 30°C (resolution: 0.1)
7 if P141 1
9 if P141 = 1
P119 2 and P120 4