EN - 44
4 mA 20 mA
P125.2
P126.2
CSG
4-20 mA input
18.3 Control setpoint calculation
18.3.1 Fixed setpoint
If P120 = 1 (1 setpoint)
In cooling mode:
- If P127 = No or outdoor sensor fault, control setpoint = P12
- If P127 = Yes (law based on outdoor temperature) and there are no outdoor sensor faults, fixed setpoint (Tout) is calculated using P121
In heating mode:
- If P131 = No or outdoor sensor fault, control setpoint = P123
- If P131 = Yes (law based on outdoor temperature) and there are no outdoor sensor faults, fixed setpoint (Tout) is calculated using P123
If P120 = 2 (2 setpoints with selection made via console)
In cooling mode:
- If P127 = No or outdoor sensor fault, control setpoint = P121 or P122 based on the selection made via the console.
- If P127 = Yes (law based on outdoor temperature) and there are no outdoor sensor faults, fixed setpoint (Tout) is calculated using P121 or
P122 based on the selection made via the console.
In heating mode:
- If P131 = no or outdoor sensor fault, control setpoint = P123 or P124 based on the selection made via the console.
- If P131 = Yes (law based on outdoor temperature) and there are no outdoor sensor faults, fixed setpoint (Tout) is calculated using P123 or
P124 based on the selection made via the console.
If P120 = 3 (2 setpoints with selection on On/Off input)
In cooling mode:
- If P127 = No or outdoor sensor fault:
- Control setpoint = P121 if on/off input open.
- Control setpoint = P122 if on/off input closed.
- If P127 = Yes (law based on outdoor temperature) and there are no outdoor sensor faults:
- Fixed setpoint (Tout) calculated using P121 if on/off input open.
- Fixed setpoint (Tout) calculated using P122 if on/off input closed.
In heating mode:
- If P131 = No or outdoor sensor fault:
- Control setpoint = P123 if on/off input open.
- Control setpoint = P124 if on/off input closed.
- If P131 = Yes (law based on outdoor temperature) and there are no outdoor sensor faults:
- Fixed setpoint (Tout) calculated using P123 if on/off input open.
- Fixed setpoint (Tout) calculated using P124 if on/off input closed.
If P120 = 4 (setpoint on 4-20 mA input)
In heating mode:
DIAGRAM 1
Displayed if P120 = 3 and HEATING mode activated:
If setpoint adjustment based on outdoor temperature = No or there is an outdoor sensor fault Control setpoint = result of diagram 1.
If the setpoint is adjusted based on the outdoor temperature = Yes and there are no faults on the outdoor sensor:
- The derived setpoint is calculated using the outdoor temperature. The result of diagram 1 is taken as the setpoint (P123 or P124).
If P120 is set to '3', P131 switches to 'No'.
- To reverse the direction of the slope, simply set P125.2 > P126.2 with a minimum difference of 5 K.
In cooling mode:
P125.2 SETPOINT FOR 4mA
HEATING -xx,x°
P126.2 SETPOINT FOR 20mA
HEATING -xx,x°
4-20 mA input
STP
4 mA 20 mA
P125.1
P126.1
CSG
STP