CIAT XtraConnect 2 - 15.7 Limitation of operation of the machines based on the outdoor temperature; 15.7.1 Minimum air temperature limit in heating mode for water-to-water units; 15.7.2 Maximum air temperature limit in heating mode for water-to-water units; 15.7.3 Maximum air temperature limit in cooling mode

CIAT XtraConnect 2
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN - 38
To reset parameter P276.1 (electric power consumed), select it then press OK. The following message appears:
Press OK to reset the energy meter.
In the case of a POWERCIAT unit consisting of two modules, only the total energy meter may be reset.
15.7 Limitation of operation of the machines based on the outdoor temperature:
15.7.1 Minimum air temperature limit in heating mode for water-to-water units
- This parameter can be set to between 25°C and 5°C in 1° increments
- Default setting: DISABLED
The unit shuts off once the outdoor temperature P225.
The unit restarts once the temperature rises to above P225 +2K.
Display:
A fault does not appear on the controller if the machine is turned off by this limit.
- To enable this function, simply enter a value between 25 and +C and press OK
15.7.2 Maximum air temperature limit in heating mode for water-to-water units:
This function is used to prohibit the machine operating in heating mode when the outdoor temperature rises above a configurable value.
- This parameter can be set to between 5 and +20°C in 1° increments 1
- Default setting: DISABLED
The unit shuts off once the outdoor temperature P225.2
The unit restarts once the temperature rises back to above P225.2 2K.
Display:
A fault does not appear on the controller if the machine is turned off by this limit.
- To enable this function, simply enter a value between 5°C and +25°C and press OK.
15.7.3 Maximum air temperature limit in cooling mode
- This parameter can be set to between 35°C and 50°C in 1° increments.
- Default setting: DISABLED
The unit shuts off once the outdoor temperature P225.1.
The unit restarts once the temperature rises back to above P225.1 - 2K.
Display:
A fault does not appear on the controller if the machine is turned off by this limit.
- To re-enable it, simply enter a value between 35°C and 50°C and press OK.
15.7.4 Minimum air temperature limit in cooling mode
This function is used to prohibit the machine operating in cooling mode when the outdoor temperature rises above a configurable value.
- This parameter can be set to between 20 and +12°C in 1° increments
- Default setting: DISABLED
The unit shuts off once the outdoor temperature P225.3.
The unit restarts once the temperature rises back to above P225.3 +2K.
P 276.1 ELEC POWER
CONSUMED xxxxKWH
RESET ELEC POWER
CONSUMED OK:CONFIRM
P225 MINI AIR TEMP
HEATING MODE DISABLED
MACHINE STOPPED HEATING MODE
LOW LIMIT EXT. TEMP
P225.2 MAXI AIR TEMP.
HEATING MODE
MACHINE STOPPED HEATING MODE
OUT. TEMP. TOO HIGH
P225.1 MAXI AIR TEMP.
COOLING MODE
MACHINE STOPPED COOLING MODE
OUT. TEMP. TOO HIGH
P225.3 MINI AIR TEMP
COOLING MODE