EN - 12
3.4 Management of the numeric codes for accessing levels 2 and 3
- Access to level 3 is direct for anyone with a PC running the program needed to communicate with Xtraconnect 2 and who connects to the
board.
- Level 2 and level 3 access codes may be obtained only from CIAT Service technicians. Please contact your local CIAT Service office.
3.5 Classification of the menus and their functions
Level 1:
● Menu: Setpoint, Unit status, Measured values, Adjustment parameters, Reading parameters, Fault memory, Programming, Communication
and Access level selection.
● Function: all functions accessible via the console: On/Off, Reset (via the fault memory menu), Heating/Cooling selection, Setpoint 1/2
selection.
Level 2:
● Menu: all level 1 menus + test mode and master/slave mode.
Level 3:
● Menu: all level 2 menus and machine parameters.
IMPORTANT: all the controller parameters are available via the reading parameters menu in read-only mode regardless of the access level
(even level 1). The list of parameters starts at P1 and ends at P811.
4 LIST OF PARAMETERS
Access level: 1 = Access to USER parameters (level 1 parameters only)
2 = Access to viewable and editable parameters (levels 1 and 2). The numeric code is
EDITABLE.
3 = Access to CIAT T
ECHNICIAN parameters (levels 1, 2 and 3). The numeric code is uneditable.
Access
level
No. Description Setting Default Display conditions
MACHINE CONFIGURATION
3
1 Refrigerant type R134a R134a
3
2 Unit type 1: Water-to-water; 2: Air-to-water 2
3
3 Number of circuits 2 - 3 2
3
8 Unit size
Condenserless 1800 - 2150 - 2500 - 2800 - 3050 -
3500 - 3600 - 3900 - 4200 - 4500 - 4800
1200 If P1 = R134a, P2 = 2 and P3 = 2
Condenserless 4850 - 5400 - 6000 - 6600 4850 If P1 = R134a, P2 = 2 and P3 = 3
1800 - 2150 - 2500 - 2800 - 3050 - 3500 - 3600 -
3900 - 4200 - 4500 - 4800
1800 If P2 = 1 and P3 = 2
3
9 Compressor start-up Star-Delta - Part Winding Star-Delta
3
15 Measurement of electrical quantities No - Yes No
3
16 Primary CT rating (module 1) 0 to 1000 A
500 A
if P2 = 1 and
P8 = 1800 to 2800
or P2 = 2, and P8 =
1800 to 2500
750 A
if P2 = 2, P3 = 2 and
P8 = 2800 to 3900 or
if P3 = 3 and
P8 = 4850, 5400
1000 A
if P2 = 1 and
P8 = 3050 to 4800 or
P2 = 2, P3 = 2 and
P8 = 4200 to 4800 or
if P3 = 3 and
P8 = 6000, 6600
If P15 = Yes
3
17 Secondary CT rating (module 1) 1 or 5 A 5 If P15 = Yes
3
18 Primary CT rating (module 2) 0 to 1000 A 500 A If P15 = Yes and P3 = 3
3
19 Secondary CT rating (module 2) 1 or 5 A 5 If P15 = Yes and P3 = 3
OPTION
2
21 Variable speed drive
1 - Without
2 - With acoustic optimisation
3 - With energy optimisation
Without
If P2 = 2 and P8 condenserless
Value 3 accessible only
if P42 No
2
24 Hydraulic module No - Yes No
If P2 = 2 and P08 condenserless
2
25 Number of pumps delivered by CIAT 1-2 0 Visible if P24 = Yes
2
26 0-10 V configurable output Not used – 3-way valve – Variable speed pump 2 Not used
Three-way valve, visible if
P2 = Water-to-water