EN - 24
To access measured values when a fault occurred, press OK.
Press + or to scroll through the faults line by line. To go back to the main menu, press the ESC button until the menu appears.
Reading for saving faults to memory.
5.9 Test mode menu
TEST mode makes it possible to shorten the time delays (without deactivating the protections) as well as jump the control whilst forcing the stages.
The other menus (measured values, parameters, fault memory, etc.) can be accessed while in test mode.
During test mode, a 'TEST MODE ON' message is sent to the other control modes (remote control console, BMS, modems, etc.) and the modes are disabled.
Accessing TEST mode via menu 8 on the local console.
Display:
Use + or to select Yes or No. Press OK to confirm your choice.
The Power LED flashes (75-25) when Yes is selected.
If compressor forcing (intake or exhaust) is selected) :
Select the desired compressor. Confirm by pressing OK.
x-EMERGENCY STOP
x-CUSTOMER FAULT
x-CIRCUIT HP x
x-CIRCUIT LP x
x-COMPRESSOR MOTOR X
x-LUBRICATION X
x-DISCHARGE T. CIRC. X
x-DESUPERHEATING x
x-MIN. OVERHEAT CX
x-MAX. OVERHEAT CX
x-FAN
x-EVAP. INLET SENSOR
x-EVAP. OUTLET SENSOR
x-INLET COND. SENSOR
x-OUTLET COND. SENSOR
x-DISCHARGE SENSOR X
x-SUCTION SENSOR X
x-HYDRAUL.MOD. SENSOR
x-EXTERNAL T.SENSOR
x-EXPANS VALVE FAULT X
x-ADD3 BOARD LINK FAULT
x-LP X SENSOR
x-HP X SENSOR
FAULT MEMORY EMPTY
HPx:xx.xb LPx:xx.xb
DIS:xxx° DESUP:xx°
EVAP WATER IN T -xx.x°
EVAP WATER OUT T -xx.x°
CDR WATER IN T –xx.x°
CDR WATER OUT T –xx.x°
SETPOINT:-xx.x°
EXTERNAL TEMP.:-xx.x°
TEST MODE
YES
TEST MODE
NO
COMP 1 TEST
COMP 2 TEST YES
COMP 3 TEST
CIRCUIT X TEST
+:INTAKE EXHAUST:
If a circuit fault occurs
If P2 = 1