EN - 22
P100 Language: used for setting the display language.
P101 Date: used for setting the date.
P102 Time: used for setting the time.
P103 Control mode: used for selecting the control mode (see
section 2).
P108 Pump 2 control: used for setting the control mode for pump
2 (see section 9).
P116 Link with AEROCONNECT controller: yes or no.
P117 Power input limit: yes or no.
P118.1 Maximum electrical power level.
P118.2 Electrical power differential.
P119 Operating mode: used for setting the operating mode and
its changeover mode.
P120 Number of setpoints: used for setting the number of
setpoints (1 or 2) and how they are controlled (see section 17).
P121 Cooling setpoint 1 (see section 17).
P122 Cooling setpoint 2 (see section 17).
P123 Heating setpoint 1 (see section 17).
P124 Heating setpoint 2 (see section 17).
P125.1 4-20 mA low setpoint (section 17).
P125.2 4-20 mA low setpoint (section 17).
P126.1 4-20 mA high setpoint (section 17).
P126.2 4-20 mA high setpoint (section 17).
P127 Adjustment of the cooling setpoint based on the outdoor
temperature (see section 17).
P128 Start of drift in cooling mode (see section 17)
P129 End of drift in cooling mode (see section 17)
.
P130 Setpoint at end of drift in cooling mode (see section 17).
P131 Adjustment of the heating setpoint based on the outdoor
temperature (see section 17).
P132 Start of drift in heating mode (see section 17)
P133 End of drift in heating mode (see section 17)
P134 Setpoint at end of drift in heating mode (see section 17).
P141 Control mode: used for setting the control mode for the
system supply and return temperature.
P142 Water loop winter safety (see section 10).
P143 Compressor stage differential.
P144 Interstage differential.
P145 Proportional coefficient (see section 17).
P146 Integral coefficient (see section 17).
P147 Derivative coefficient (see section 17).
P148 Time coefficient (see section 17).
P149 Additional exhaust coefficient.
P150/P151 Control with compensation (see section 17).
P154 Enable storage control: yes or no.
P155 Storage control differential (see section 17).
P170 Intercircuit start time.
P175 Compressor load shedding (see section 6).
Fan management:
P181 HP control setpoint (see section 18).
P182 Outdoor air temperature for forced fan operation (see
section 18).
P185
Circuit 1 fan stage differential (see section 18).
P186 Circuit 1 fan interstage differential (see section 18).
P187 Circuit 2 fan stage differential (see section 18).
P188 Circuit 2 fan interstage differential (see section 18).
P189 Circuit 3 fan stage differential (see section 18).
P190 Circuit 3 fan interstage differential (see section 18).
HP control:
P193 Enable HP control shift for recovery on the condensers: yes
or no.
P196 Differential requiring return to standard condensing
pressure control (see section 18).
P197 Condenser water outlet temperature corresponding to a
signal voltage of 0 V for the three-way valve.
P198 Condenser water outlet temperature corresponding to a
signal voltage of 10 V for the three-way valve.
P220 Winter protection outdoor temperature (see section 10).
P221 Ambient temperature at which the hydraulic module's
defrost heater is turned on (see section 10).
P222 Winter protection outdoor temperature differential (see
section 10).
P225 Minimum outdoor temperature below which HEATING is no
longer authorised.
P225.1 Maximum outdoor temperature above which COOLING is
no longer authorised.
P225.2 Maximum outdoor temperature above which HEATING is
no longer authorised.
P225.3 Minimum outdoor temperature below which COOLING is no
longer authorised.
P227/P228/P229 Authorisation for compressor stages to turn on.
5.7 Reading parameters menu
To enter the READING PARAMETERS menu, press + or – to position the cursor on 6 then press OK.
The display shows the list of reading parameters.
Example:
Press + or – to scroll through the parameters two lines at a time.
The values of these parameters cannot be changed.
To return to the main menu, press the ESC button repeatedly.
Important:
The reading parameters menu allows read-only access to all parameters in the other menus and to the following parameters as well:
P250 LED test: used to turn on the console LEDs corresponding
to the machine configuration.
P251 Control setpoint: displays the setpoint used by the
controller.
P252 P251 Outdoor air temperature.
P253 Evaporator water inlet temperature.
P254.1 Evaporator water outlet temperature (module 1).
P254.2 Evaporator water outlet temperature (module 2).
P257 Condenser water inlet temperature (water-to-water unit).
P258 Condenser water outlet temperature (water-to-water unit).
P261.1 Manifold water outlet temperature.
P261.2 Master/slave water outlet temperature.
P265 Air temperature inside the hydraulic module.
P270 Controller action time delay.
P272 Oil warm-up time.
P273.1 Supply voltage (module 1).
P129 END OF COOLING
DRIFT xx°
Pxxx EVAP. WATER INLET
TEMP. -12.5°
6-READING PARAMETERS