CIAT XtraConnect 2 - 5.8 Fault memory menu

CIAT XtraConnect 2
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN - 23
P273.2 Supply voltage (module 2).
P274.1 Machine current input.
P274.2 Current input (module 1).
P274.3 Current input (module 2).
P275.1 Machine power input.
P275.2 Power input (module 1).
P275.3 Power input (module 2).
P276.1 Electricity consumption.
P276.2 Electricity consumption (module 1).
P276.3 Electricity consumption (module 2).
P285 Heating mode runtime (in hours).
P286 Cooling mode runtime (in hours).
P287 Pump 1 runtime (in hours).
P288 Pump 2 runtime (in hours).
P289 Number of times P99 (parameter lock) has been accessed.
P290 Number of water flow switch cut-outs.
Circuit 1 information:
P300 Circuit high pressure value.
P300.1 Circuit 1 HP control setpoint
P301 Corresponding circuit 1 condensing temperature for the
above pressure value.
P302.1 Circuit 1 discharge temperature value.
P303.1 Circuit 1 condenser desuperheat temperature
(= discharge temperature condensation dew point temperature).
P304 Circuit 1 low pressure value.
P305 Corresponding circuit 1 evaporating temperature for the
above pressure value.
P306 Circuit 1 compressor suction temperature.
P307 Circuit 1 superheat temperature (circuit 1 suction
temperature above circuit 1 evaporating temperature).
P309 Number of cut-outs caused by a low pressure fault on circuit
1 in 24 hours.
P316 Number of circuit starts.
P317 Circuit 1 runtime.
P318 Circuit 1 short-cycle protection.
P324.1 Number of cut-outs caused by a discharge temperature
fault on circuit 1 in 24 hours.
Circuit 2 information:
P330 to P354 same as P300 to P324.1 but for circuit 2.
Circuit 3 information:
P360 to P384 same as P300 to P324.1 but for circuit 3.
Inputs:
P400 State of unit automatic operation control input (open or
closed).
P401 State of pump automatic operation control input (open or
closed).
P402 Setpoint selection input state (1 or 2).
P403 Water flow input state.
P404 Fan fault input state.
P405 Operating mode input state.
P406.1 State of phase controller input (circuits 1 and 2).
P406.2 State of phase controller input (circuit 3).
P408
Pump 1 input state.
P409 Pump 2 input state.
P410 Manual operation input state for unit (remote condenser):
P411 Customer input state (general fault).
P412 Compressor 1 fault input state.
P413.1 State of compressor 1 load shedding input.
P413.2 State of compressor 2 load shedding input.
P413.3 State of compressor 3 load shedding input.
P418 High-pressure switch 1 input state.
P421 Stage 2 fault input state.
P422 High-pressure switch 2 input state.
P425 Stage fault input state.
P426 Stage load shedding input state.
P427 High-pressure switch 3 input state.
Outputs:
P447 Voltage of HP control drive signal for circuit 1.
P448 Voltage of HP control drive signal for circuit 2.
P449 Voltage of HP control drive signal for circuit 3.
P450 Pump 1 contact output state.
P451 Pump 2 contact output state.
P455 State of evaporator defrost heater contact output.
P456 State of pipe heat trace cable contact output.
P457 State of the contact output for the hydraulic module's
electric heating elements.
P460/P475/P490 State of circuit 1/2/3 fan stage 1 contact output.
P461/P476/P491 State of circuit 1/2/3 fan stage 2 contact output.
P462/P477/P492 State of circuit 1/2/3 fan stage 3 contact output.
P463/P478/P493 State of circuit 1/2/3 fan stage 4 contact output.
P464/P479/P494 State of circuit 1/2/3 fan stage 5 contact output.
P465/P480/P495 State of circuit 1/2/3 fan stage 6 contact output.
P466/P481/P496 State of compressor 1/2/3 winding 1 contact
output.
P467/P482/P497 State of compressor 1/2/3 winding 2 contact
output.
P470/P485/P500 Compressor 1/2/3 reset contact.
P471/P486/P501 Compressor 1/2/3 intake valve contact.
P472/P487/P502 Compressor 1/2/3 exhaust valve contact.
P473/P488/P503 Circuit 1/2/3 liquid valve contact.
P474/P489/P504 Circuit 1/2/3 HPS valve contact.
P555 CPU version number.
P556 Console version number.
P557.2 ADD3 board version number.
P557.3 ADD3 board version number (circuit 3).
P557.4 ADD1 board version number (circuit 3).
P570 "SO" order number.
P571 MO number.
P572 Machine identification name.
P573 Machine identification number.
5.8 Fault memory menu
This menu records the last 20 faults on the machine and the associated values measured at the time the faults occurred.
To enter the FAULT MEMORY menu, use the + or buttons to position the cursor on 7 then press OK.
The list of faults appears on the display. The top left of the screen flashes first, followed by the line being queried. Press the + or buttons to
scroll through the faults.
Accessing the fault memory.
Below is a list partial of fault memory messages for all fault types (main circuit fault, main unit fault, temporary fault).
Important: Faults can be manually reset from this menu only.
7-HP1 PRESSURE SWITCH
Xx/xx/xxxx xxHxx
x-POWER CUT
x-PHASE CONTROLLER
x-WATER FLOW
x-ANTIFREEZE/WATER
x-PUMP X FAULT