EN - 5
+
TR1
SP1
PL1
J4J2 J3
J6J8
J5J7
J9J11 J10
W3
J14 J12J13
D46 D48D50 D52
121110987654321
12345678910111213141516
1110987654321
121110987654321 1110987654321321321 321
43214321
8642
7531
12345 123
CIAT GAMME CONNECT2
Locking the console
Note: available only on the local console located on the unit.
The console is set by default to 'unlocked'.
The lock state is saved in the event of a mains power failure.
If locking mode is enabled while modifying a parameter, any changes entered are not saved and the parameter reverts to its initial setting.
To lock the console, simultaneously press and hold + and – for 5 seconds (possible in any menu on the console).
The following message appears for 5 seconds then the display returns to unit status mode (test mode is disabled):
It is now possible to make any changes via the local console. Any attempts to enter changes will cause the following message to appear for 3
seconds.
The console is unlocked in the same manner, i.e. by pressing and holding + and – for 5 seconds. Doing so causes the following message to
appear for 3 seconds:
2.2 Description of the motherboard
SWITCH W3
End-of-line resistance for two-wire RS485 link. The switch must be
set to the left for the last unit on the loop and to the right for the
others.
TERMINAL BLOCK J2 (analogue outputs)
1-2: 0-10 V output for circuit 1 fan speed control
(+ on terminal 1).
3-4: 0-10 V output for circuit 2 fan speed control
(+ on terminal 3).
4-5: 0-10 V output for common fan speed control
(+ on terminal 5).
TERMINAL BLOCK J3 (on/off inputs)
1: Circuit fault output common.
2: Circuit 1 fault output.
3: Circuit 2 fault output.
4: Common, inverter compressor 1 contactor and heater control.
5: Evaporator defrost heater control.
6: Pipe heat trace cable control.
7: Hydraulic module heater control.
8: Compressor 1 intake valve or inverter compressor 1 contactor
control.
9: Compressor 2 intake valve or inverter compressor 2 contactor
phase.
10: Compressor 2 intake valve or inverter compressor 2 contactor
control.
11: Fault output common.
12: NC contact for fault output.
13: NO contact for fault output.
14: Common for pumps.
15: Pump 1 control.
16: Pump 2 control.
TERMINAL BLOCK J4 (power supply)
1: 230 V board power supply - Line.
2: 230 V board power supply - Neutral.
3: Earth.
LOCKED
DISPLAY PANEL
LOCKED
DISPLAY PANEL
UNLOCKED
DISPLAY PANEL