AFQm
Instruction Manual
11.- TECHNICAL FEATURES
Mains voltage
Rated voltage Un
AFQm-3WF-xxxx-480 AFQm-4WF-xxxx-400
208 ... 480 V~ Ph-Ph ± 10% 208 ... 400 V~ Ph-Ph ± 10%
AFQm-3WF-xxxx-690 AFQm-4WF-xxxx-550
230 ... 690 V~ Ph-Ph ± 10% 230 ... 550 V~ Ph-Ph ± 10%
Frequency Fn 50 / 60 Hz ± 5%
Maximum THD V 25 %
Earthing system TN, TT
Power
AFQm-xxx-030M AFQm-xxx-060M
AFQm-xxx-100R
AFQm-xxx-100M
Maximum consumption 650 W 1300 W 2070 W
Maximum current (phase) 30 A RMS 60 A RMS 100 A RMS
Maximum current (neutral) 90 A RMS 180 A RMS 300 A RMS
Crest factor (current) 2:1 2:1 2:1
Maximum
power
480V
AFQm-3WF-030M AFQm-3WF-060M
AFQm-3WF-100R
AFQm-3WF-100M
22906 VA 45812 VA 76300 VA
400V
AFQm-4WF-030M AFQm-4WF-060M
AFQm-4WF-100R
AFQm-4WF-100M
20700 VA 41400 VA 69000 VA
AFQm-xxx-100C AFQm-xxx-200C
Rated insulation voltage Ui 480 V 480 V
Impulse withstand voltage Uimp 4kV, CAT III Class 1 4kV, CAT III Class 1
Rated current (phase) Ina phase 100 A 200 A
Rated current (neutral) Ina neutral 300 A 600 A
Short-time withstand current Icw 3.5 kA 1 second 3.5 kA 1 second
Peak current Ipk 84 kA peak 84 kA peak
Rated conditional short-circuit current Icc 40 kA 40 kA
Simultaneity RDF 1 1
Maximum consumption 2070 W 4140 W
Maximum current (phase) 100 A RMS 200 A RMS
Maximum current (neutral) 300 A RMS 600 A RMS
Crest factor (current) 2:1 2:1
Maximum power
480V
AFQm-3WF-100C AFQm-3WF-200C
76300 VA 152600 VA
400V
AFQm-4WF-100C AFQm-4WF-200C
69000 VA 138000 VA
AFQm-xxx-300C AFQm-xxx-400C
Rated insulation voltage Ui 480 V 480 V
Impulse withstand voltage Uimp 4kV, CAT III Class 1 4kV, CAT III Class 1
Rated current (phase) Ina phase 300 A 400 A
Rated current (neutral) Ina neutral 900 A 1200 A
Short-time withstand current Icw 3.5 kA 1 second 3.5 kA 1 second
Peak current Ipk 84 kA peak 84 kA peak