70
AFQm
Instruction Manual
7.5.- HARMONICS SELECTION
Note: This screen is not visible on the “slave” devices.
Note: The screen that appears if you have selected the operating mode FREQ: Frequency mode (“7.4.-
WORKING MODE”)
The harmonics to be filtered are selected in this screen, Figure 74.
Figure 74: Configuration screen: Harmonic selection.
Press the key to access the next configuration step
Press the key to access the main screen of the device without saving the configuration values.
7.6.- OPERATING LIMITS
Note: This screen is not visible on the “slave” devices.
In this screen, Figure 75, the operating limits of the device are configured:
Figure 75: Configuration screen: Operating limits.
● Min current
The minimum load current to start the active filter is configured with this parameter. Minimum current
feature is used to increase the system efficiency, by stopping the filter when required. The AFQm will
stop when the load current is below the entered value and will start when it is higher.