Table 23 (Cont.) : Warnings messages.
Alarm and event messages
Corrective
action
Confirm that the connections are correct.
Reverse power
Description The power value measured is negative (generated power), which might indicate that the transformers
have been connected inversely.
Corrective
action
Confirm that the connections are correct.
Wxxx
Description Internal error.
Corrective
action
Contact the Technical Assistance Service.
Parallel filter in alarm
Description This is a fault in one or more slaves.
Corrective
action
The device does not stop and adjusts its operation to the number of available slaves. On the slave
device status screen, 6.21.- SLAVE DEVICE STATUS you can view the status and alarms for each
filter. If there is a communications error with any of the slaves, stop the devices and check the com-
munications wiring.
6.18.- TEMPERATURE
Note: This screen is not visible on the “slave” devices.
In this screen, Figure 62, displays the device’s temperature range for inductances and IGBTs.
Figure 62: Temperature.
The screen displays:
Ok, correct temperature.
Hi, high temperature.
Low, low temperature.
Use the and keys to navigate through the different display screens.