EasyManua.ls Logo

Circutor AFQm 30 A - Connecting Cabinets

Circutor AFQm 30 A
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
Instruction Manual
AFQm
3.8.2.- CONNECTING CABINETS
Note: The 200A (AFQm-xxx-200C), 300A (AFQm-xxx-300C) and 400A (AFQm-xxx-400C) cabinets
are made up of 2, 3 and 4 100A devices in parallel. Both the parallel configuration and connection are
factory-set.
The 140A (AFQm-xxx-140C), 210A (AFQm-xxx-210C) and 280A (AFQm-xxx-280C) cabinets are made
up of 2, 3 and 4 70A devices in parallel.
Note: Both the parallel configuration and connection are factory-set.
To connect multiple cabinets in parallel, follow these steps:
1.- Select the cabinet that is to contain the “master device.
2.- Connect the “master cabinet. The current transformers are only connected to the “master cabinet.
3.- Connect the “slave cabinets.
4.- Connect all of the devices using the communication cables (Table 16).
Connect the OUT terminal from the final slave device in the “master cabinet to the IN terminal from
the “master device of the following cabinet, and the OUT terminal from the final “slave” device in this
cabinet to the IN terminal of the “master device of the following cabinet, and so on (Figure 31).
Master Slave Slave
(*)
Connections already included in the cabinets
IN
OUT
2
3
2
3
IN
OUT
2
3
2
3
OUT
IN
2
3
IN
2
3
OUT
2
3
2
3
AFQm-xxx-200C
(*)
(*)
OUT
IN
2
3
IN
2
3
OUT
2
3
2
3
(*)
ON
RBUS
ON
RBUS
ON
RBUS
ON
RBUS
ON
RBUS
ON
RBUS
Figure 31:Connecting 3 devices in parallel, using the communication cable (200 A Master AFQm).
5.- Configure the installation in the “master device (see 7. CONFIGURATION”.
6.- Complete the configuration of the slave devices (see “7.- CONFIGURATION).
7.- Enable the terminator switch for parallel connection, RBUS (Terminal No 2 of Table 13) in the bus
end devices only. Then disable in the other devices.

Table of Contents