71
Instruction Manual
AFQm
Range of values:
Minimum value: 0 A
Maximum value: 5000 A
Current limit
This parameter allows the maximum power of the active filter to be limited. The value is configured as
a percentage with respect to the device's rated power.
Range of values:
Minimum value: 20%
Maximum value: 100%
Press the key to access the next configuration step
Press the key to access the main screen of the device without saving the configuration values.
7.7.- cos Φ
Note: This screen is not visible on the “slave” devices.
The device has two reactive power compensation modes (Figure 76).
Figure 76: Configuration screen: cos Φ (Mode 1 and Mode 2).
Mode 1
In this mode, cos Φ is set to a fixed value. The device will attempt to ensure that the reactive power on
the mains side corresponds to the specified cos Φ.
Range of values: 0.7... -0.7
Mode 2
In this mode, two limits are defined to form an acceptance range. The device will adjust the reactive
power on the mains side to keep cos Φ within the specified acceptance range.