EasyManua.ls Logo

Circutor AFQm 30 A - Page 105

Circutor AFQm 30 A
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
105
Instruction Manual
AFQm
RS-485 Communications
Field bus RS-485
Communications protocol Modbus RTU
Baud rate 9600 bps
Stop bits 1
Parity none
Ethernet communications
Network protocol TCP/IP, Modbus TCP
User interface
Display
3.5” TFT colour touch screen
Web server and datalogger
Environmental features
Environmental conditions Indoor conditioned IEC 60721-3-3
Operating temperature -10ºC ... +45ºC
Storage temperature -20ºC... +50ºC
Relative humidity (with no condensation) 0 ... 95%
Maximum altitude
3000 m a.s.l. ( 2000 m a.s.l. without performance degradation)
AFQm-3WF-xxxC-690, AFQm-4WF-xxxC-550
5000 m s.n.m.
Protection degree IP20
Overvoltage category
OVC III 300V
AFQm-3WF-xxxC-690, AFQm-4WF-xxxC-550
OVC III 600V
AFQm-xxx-070C, AFQm-xxx-100C, AFQm-xxx-140C, AFQm-xxx-200C,
AFQm-xxx-210C, AFQm-xxx-280C, AFQm-xxx-300C, AFQm-xxx-400C
Pollution degree 2
Impact resistance IK 10
Electromagnetic compatibility Installation in type-A environments
Standards
Electromagnetic compatibility (CEM). Part 6-4: Generic standards. Emissions stand-
ard for industrial environments. (IEC 61000-6-4:2006).
UNE-EN 61000-6-4:2007
Industrial, scientific and medical equipment - Radio-frequency disturbance charac-
teristics - Limits and methods of measurement
UNE-EN 55011:2011
Electromagnetic compatibility (CEM). Part 6-2: Generic standards. Immunity for in-
dustrial environments.
UNE-EN 61000-6-2:2006
Safety requirements for power electronic converter systems and equipment - Part 1:
General (Endorsed by AENOR in November of 2012.)
EN 62477-1:2012
Low-voltage switchgear and controlgear assemblies - Part 1: General rules IEC 61439-1:2011