110
AFQm
Instruction Manual
AFQm-xxx-070C, AFQm-xxx-100C, AFQm-xxx-140C, AFQm-xxx-200C,
AFQm-xxx-210C, AFQm-xxx-280C, AFQm-xxx-300C, AFQm-xxx-400C
Dimensions (mm) Figure 108
Weight
AFQm-xxx-070C AFQm-xxx-100C AFQm-xxx-140C AFQm-xxx-200C
192 kg 190 kg 249 kg 245 kg
AFQm-xxx-210C AFQm-xxx-280C AFQm-xxx-300C AFQm-xxx-400C
306 kg 363 kg 300 kg 355 kg
Enclosure Free-standing sheet steel cabinet, for installation indoors, without removable parts.
Noise
AFQm-xxx-070C AFQm-xxx-100C AFQm-xxx-140C AFQm-xxx-200C
< 70 dBA < 60 dBA < 73 dBA < 63 dBA
AFQm-xxx-210C AFQm-xxx-280C AFQm-xxx-300C AFQm-xxx-400C
< 76 dBA < 79 dBA < 66 dBA < 69 dBA
Connections
Current
Type
Spring 2.5 mm
2
Earth
(10)
Type
Ring terminal 8 mm 10 Nm Hex 13 mm
Ethernet
Type
RJ-45
Mains
Filter
Bar
(11)
Drill Screw
Terminal
width
AFQm-xxx-070C
30x3
1xM10 M10 8.8
≤ 32 mm
45 Nm
AFQm-xxx-100C
AFQm-xxx-140C
40x5
≤ 37 mm
AFQm-xxx-200C
AFQm-xxx-210C
AFQm-xxx-280C
AFQm-xxx-300C
40x10
AFQm-xxx-400C
Neutral
AFQm-xxx-070C
50x10
2xM10
M10 8.8
≤ 32 mm
45 Nm
AFQm-xxx-100C
AFQm-xxx-140C
80x10
≤ 37 mm
AFQm-xxx-200C
AFQm-xxx-210C
AFQm-xxx-280C
AFQm-xxx-300C
100x10 3xM10
AFQm-xxx-400C
(10)
If the phase conductors exceed 32 mm
2
, the earth conductor can be the half of the cross-section of the phase conduc-
tors.
(11)
The connection bars allow the cables to be placed on both sides, and two cables may be routed through each drill hole.