84
AFQm
Instruction Manual
Table 37 (Cont.): Modbus memory map: Filter messages (Table 2).
Bit Description
0x00000008 L3 overcurrent alarm
0x00000010 L1 overvoltage alarm
0x00000020 L2 overvoltage alarm
0x00000040 L3 overvoltage alarm
0x00004000 Temperature IGBT 1 alarm
0x00008000 Temperature Inductor 1 alarm
0x00010000 Initial Conditions Error
0x00020000 Resonance Alarm
0x00100000 Contactor faults
0x00200000 Temperature Inductor 2 alarm
Table 38:Modbus memory map: Filter messages (Table 3).
Parameter Address
Initial Conditions for which the device does not start up. 
(6)
108
Bit Description
0x0001 Discharging DC bus
0x0002 Minimum Mains Voltage
0x0004 Minimum temperature value
0x0008 Frequency error
0x0010 Charging DC bus
0x0020 Minimum DC bus voltage
0x0040 DC Bus imbalance
0x0080 The device does not communicate
0x0100 Polarity Error
0x0200 Minimum load current
0x0400 Maximum charge current
(6) 
 For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
Table 39:Modbus memory map: Filter messages (Table 4).
Parameter Address
AFQm status 
(7)
104
Status (Decimal value) Description
0 Start-up
10, 20, 30 Calibration
40 Relay test
50 Expect communications
60 Configuration
100 Start
200 Initial conditions
300 Stop
400 Synchronising
500 DC bus load
600 Operation
666 Power off
700 Alarm
(7) 
 For a system with devices in parallel, the parameter value is that of the device connected with RS-485.