----- Supply network analyzer CVM 96 Ethernet -------- ----- Page No. 40
EXAMPLE
INQUIRY 0A 04 00 00 00 0A 71 76
0A CVM 96 peripheral number, 10 in decimal
04 Reading function
00 00 Initial address (first register)
00 0A Number of registers to be read
7176 CRC character
ANSWER 0A 04 14 00 00 08 4D 00 00 23 28 00 00 0F A0 00 00 00
90 00 00 00 60 CB 2E
0A CVM 96 number , 10 in decimal
04 Reading function – the one use for the inquiry
14 Bytes received (20)
00 00 08 4D V 1x10 (register 00 Hex), in decimal 212.5 V
00 00 23 28 mA 1, in decimal 9000 mA
00 00 0F A0 W 1, in decimal 4000 W
00 00 00 90 varL 1, in decimal 144 varL
00 00 00 60 PF 1 x 100, in decimal 96 PF
CB 2E CRC character