Chapter 1 Install the Shelf and Backplane Cable
NTP-A2 Install the Shelf Assembly
Note The fan-tray assembly is shipped separately.
Step 5 Return to your originating procedure (NTP).
DLP-A2 Inspect the Shelf Assembly
Step 1 Open the shelf using the pinned hex key. For more information, see the “DLP-A8 Open the Front Cabinet
Compartment (Door)” task on page 1-12.
Step 2 Verify the following:
• Pins are not bent or broken.
• Frame is not bent.
Step 3 If the pins are bent or broken, or the frame is bent, call your Cisco sales engineer for a replacement.
Step 4 Close the front door before installing.
Step 5 Return to your originating procedure (NTP).
NTP-A2 Install the Shelf Assembly
Purpose This task verifies that all parts of the shelf assembly are in good condition.
Tools/Equipment Pinned hex (Allen) key for front door
Prerequisite Procedures DLP-A1 Unpack and Verify the Shelf Assembly, page 1-4
Required/As Needed Required
Onsite/Remote Onsite
Security Level None
Purpose This procedure describes how to reverse the mounting bracket and mount
shelf assemblies in a rack.
Tools/Equipment #2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Pinned hex key
Two set screws (48-1003-XX)
Prerequisite Procedures NTP-A1 Unpack and Inspect the ONS 15454 Shelf Assembly, page 1-4
Required/As Needed Required
Onsite/Remote Onsite
Security Level None