Data creazione 10/09/03 DS03I009GB--00 Pagina 21 di 59
Configuration Unit
Compressors
Add Code Description UOM Pass
131/CMP hp2enabled
Enable HP pre-alarm 2
The pre-alarm disconnects power from the circuit so as to avoid shutting
down the unit due to the HP alarm, when the threshold set for parameter
193 is exceeded
YES-
NO
2
132/CMP nprehp2hour
Max number of HP pre-alarm 2
When the number of activations/hour indicated is exceeded, an alarm with
manual reset is activated on the circuit
Num 2
133/CMP hp1enabled
Enable HP pre-alarm 1
The pre-alarm operates the fan at the maximum (in cooling mode) so as to
avoid shutting down the unit due to the HP alarm, when the threshold set
for parameter 233 is exceeded
YES-
NO
2
134/CMP Ip1enabled
Enable LP pre-alarm
The pre-alarm disconnects power from the circuit so as to avoid shutting
down the unit due to the low pressure alarm, when the threshold set for
parameter 195 is exceeded
YES-
NO
2
135/CEN npreLp1hour
Maximum number LP pre-alarms / hour
When the number of activations/hour indicated is exceeded, an alarm with
manual reset is activated on the circuit
Num 1
136/CMP maxlphour
Maximum number LP alarms / hour
When the number of activations/hour indicated is exceeded, an alarm with
manual reset is activated on the circuit
Num 1
137/CMP bypmincool
Low pressure bypass time in cooling
Time, counted from when each compressor in the circuit starts, during
which the activation of the pressure switch is ignored.
Sec 1
138/CMP bypminheat
Low pressure bypass in heating
Time, counted from when each compressor in the circuit starts, during
which the activation of the pressure switch is ignored.
Sec 1
140/CMP bplpon
Low pressure alarm bypass in stable operation
Delay time for the minimum pressure switch
Sec 2
167/CMP weighthour
Weight of the hours
Contribution of the total number of compressor operating hours in the
calculation of the rotations
num 2
168/CMP weightstart
Weight of the starts
Contribution of the total number of compressor starts in the calculation of
the rotations
num 2
178/CMP valvemode
Polarity of the reversing valve
0= energised in cooling
1= energised in heating
2
188/CMP pump_down
Enable pump_down
0= Not enabled
1= Enabled at compressor start
2= Enabled at compressor stop
3= Enabled at compressor start and stop
1