Data creazione 10/09/03 DS03I009GB--00 Pagina 22 di 59
189/CMP setprehp2
High pressure pre-alarm 2 set point
HP pre-alarm 2 activation threshold
Bar 1
190/CMP diffhp2
High pressure pre-alarm 2 reset differential
Bar 1
191/CMP setprelp1
Low pressure pre-alarm 1 set point
Low pressure pre-alarm 1 activation threshold
Bar 1
192/CMP difflp1
Low pressure pre-alarm 1 reset differential
Bar 1
193/CMP deltapmax Maximum value of the evap / condenser pressure difference.
Threshold for the pressure difference between the gas intake and
discharge that stops the circuit, after the time indicated for parameter 199
Bar 2
194/CMP scandeltap
Scan time for pressure difference
The system checks at preset intervals (the interval being set by this
parameter) the differential between the gas intake and discharge
pressure.
Sec 1
195/CMP tmaxdeltap
Maximum time at P diff. > Max P diff.
Time that the circuit remains at the maximum pressure differential
between intake and discharge before stopping
Sec 1
196/CMP bptcstart
Compressor overload bypass from power up
Time in which the compressor overload alarm is ignored from power up
(during this time the compressor cannot be activated in any case)
Sec 1
197/CMP timeon-on
Minimum time between 2 starts of the same compressor
Minimum time that must elapse between successive starts of the same
compressor.
Sec 1
198/CMP timeoff-on
Minimum time between compressor stop and start
Minimum time that must elapse from when a compressor stops to when it
starts again.
Sec 1
199/CMP tstarting
Minimum time between starts of different compressors
Sec 1
200/CMP trelease
Minimum time between stops of different compressors
Sec 1
229/CMP smaxprec
HP pre-alarm 1 activation threshold
HP pre-alarm 1 activation threshold (maximum ventilation)
Bar 1
230/CMP diffmaxprec
HP pre-alarm 1 reset differential
Bar 1