Data creazione 10/09/03 DS03I009GB--00 Pagina 23 di 59
Configuration Unit
Evaporators
Add Code Description UOM Pass
37/EVA SetResist
Antifreeze heater set point
Activation threshold for the antifreeze heaters
°C 0
39/EVA
ALLFreeze Antifreeze alarm set point
Activation threshold for the alarm antifreeze
°C 0
41/EVA
PreAF Antifreeze pre-alarm set point
Antifreeze pre-alarm activation threshold
°C 0
231/EVA
IsPreAF Antifreeze pre-alarm reset hysteresis
°C 1
233/EVA
IstAllFreeze
Hysteresis for resetting the antifreeze alarm °C 1
235/EVA
RitComp Delay compressors from start pump
Minimum time between the activation of the water pump and the possible
activation of the compressors
Sec 1
237/EVA
BypassFlusso Flow alarm bypass from start pump
Time counted from the start of the water pump, during which the no water
flow alarm is ignored.
Sec 1
239/EVA
RitPompaOff Delay stop pump from unit OFF
Time that must elapse between when the unit is switched OFF and the
pump stops.
Sec 1
241/EVA
TimeStartPump Pump ON time
Determines the minimum operating time of the circulating pump, when this
is activated by the MAINTENANCE function.
Sec 1
243/EVA
TscanMant Maintenance scan time
Sets the interval between two starts of the circulating pump in
MAINTENANCE operation
Sec 1
245/EVA
MinFreeze Minimum value of the antifreeze set point
Minimum limit for setting the activation threshold for the antifreeze alarm
and the antifreeze heaters.
°C 1
248/EVA
MaxFreeze Maximum value of the antifreeze set point
Maximum limit for setting the activation threshold for the antifreeze alarm
and the antifreeze heaters
°C 1
251/EVA
BypassFreeze Antifreeze alarm bypass time
Time counted from the start of the unit in heating mode, during which the
antifreeze alarm is ignored.
Sec 1