Data creazione 10/09/03 DS03I009GB--00 Pagina 25 di 59
211/CMP
tmaxcntdfr Maximum defrost delay count time
Time limit that cannot be exceeded in the calculations performed by the
system when determining the delay between the activation of the timer
and the actual defrost.
Sec 1
212/CMP
textmindly Outside temperature for minimum defrost delay
Temperature of the outside air at which the defrost delay is set to the
minimum (equal to the value of parameter 214) This value must be greater
than the value set for parameter 217
°C 1
213/CMP
textmaxdly Outside temperature for maximum defrost delay
Temperature of the outside air at which the defrost delay is set to the
maximum (equal to the value of parameter 215). This value must be lower
than the value set for parameter 216
°C 1
214/CMP
timedrain Coil dripping time
Time the compressors stop for after the defrost, to allow the water to drip
from the coils.
Sec 1
215/CMP
textdfr Outside temperature threshold for fan activation
Outside air temperature above which the fans are started, during the
dripping phase, so as to assist the process.
°C 1
216/CMP
timefandfr Fan activation time
Duration of fan operation after the defrost
Sec 1
217/CMP
pdfr Force defrost pressure
Once having reached this evaporation pressure threshold, the defrost is
forced to start (if the count is as active for at least the value set for
parameter 222)
Bar 1
218/CMP
tfdfr Minimum force defrost count time
Minimum time after which the defrost can be forced on due to minimum
pressure.
°C 1