Data creazione 10/09/03 DS03I009GB--00 Pagina 26 di 59
Configuration Unit
Fans
Add Code Description UOM Pass
172/CMP
tstartup Fan start time
Duration of the fan start-up phase.
Sec 1
173/CMP
tbycutoff Minimum operating time from compressor start
Time that the fans are operated for even without the required pressure
conditions.
Sec 1
174/CMP
maxfan Maximum fan speed
Maximum value allowed for the fan control signal.
% 1
175/CMP
minfan Minimum fan speed
Minimum value allowed for the fan control signal
% 1
176/CMP
maxstartup Fan speed at start
Speed of the fan during the start-up time
% 1
177/CMP
typece Type of condenser
Air- or water-cooled condenser
2
219/CMP
fanpfcorr
no meaning 2
220/CMP
onfancool Pressure threshold for switching fans on with compressor off
This function allows the fans to be operated even when the compressors
are off, if the pressure exceeds, due to a high outside temperature, the set
threshold
Bar 1
221/CMP
onfanheat Pressure threshold for switching fans on with compressor off
Not active
Bar 1
222/CMP
maxfanheat Pressure threshold for maximum fan speed in heating
Pressure value corresponding to the point of maximum fan speed. (At
higher pressure values the speed decreases)
The value entered must be lower than the value set for par. 227.
Bar 1
223/CMP
minfanheat Pressure threshold for minimum fan speed in heating
Pressure value corresponding to the point of minimum fan speed. (At
lower pressure values the speed increases).
The value must be higher than the value set for par. 226
Bar 1
224/CMP
maxfancool Pressure threshold for maximum fan speed in cooling
Pressure value corresponding to the point of maximum fan speed. (At
lower pressure values the speed decreases)
The value must be higher than the value set for par. 229.
Bar 1
225/CMP
minfancool Pressure threshold for minimum fan speed in cooling
Pressure value corresponding to the point of minimum fan speed. (At
higher pressure values the speed increases).
The value must be lower than the value set for par. 228
Bar 1
226/CMP
cutoffheat Pressure threshold to stop fans in heating
Pressure threshold at which the fans (already at minimum speed) are
stopped.
The value must be higher than the value set for par. 227
Bar 1
227/CMP
cutoffcool Pressure threshold to stop fans in cooling
Pressure threshold at which the fans (already at minimum speed) are
stopped.
The value must be lower than the value set for par. 229
Bar 1
228/CMP
timeoffv Condenser water flow alarm bypass time
Corresponds to the opening time of the water valve.
Active if parameter 181 is set to 1.
Sec 1