Data creazione 10/09/03 DS03I009GB--00 Pagina 27 di 59
Configuration Unit
Various
Add Code Description UOM Pass
8/CEN EnReversCycle
Enable heat pump
Enable the unit for reverse-cycle operation
2
12/CEN
RemoteMode Enable remote mode
Enable the remote control from digital inputs or from the supervisor
system via the serial protocol.
1
38/CEN
KPUMP Enable pump control for rotation
With KPUMP=1, the system, when choosing the next step to be activated
or deactivated, will consider which circuit pumps are already on, giving
these the priority.
2
67/CEN
ParOffremEN Enable remote ON-OFF
Enable the remote control from digital inputs or from the supervisor
system via the serial protocol.
1
84/CEN
INRecupEn Enable recovery
Enable the recovery activation digital input.
85/CEN
TinEn Configure the use of the central module inlet temperature probe
The inlet temperature probe on the central module can be configured as
“no probe”, display-only or alternatively as a probe that is used in the
temperature control actions.
2
99/CEN
Tstarting Minimum time between the activation of different steps
Minimum time between the activation of two different capacity-control
steps by the temperature controller
Sec 1
100/CEN
Trelease Minimum time between the deactivation of different steps
Minimum time between the deactivation of two different capacity-control
steps by the temperature controller
Sec 1
127/CEN
TimeStartPump Minimum pump start time in maintenance
130/CEN
TrunningCP Time for compressors to reach stable operation
Estimate of the time required for a compressor to reach stable operation,
from starting.
Sec 1