Data creazione 10/09/03 DS03I009GB--00 Pagina 28 di 59
Configuration Multi
Comp
Add Code Description UOM Pass
141/CMP rotenabled
Enable rotation in the circuit*
Used to define whether the compressors in the same “compressor
module” can be rotated or not.
2
142/CMP numerocp
Number of compressors*
Defines the number of compressors in the same “compressor
module”
num 2
143/CMP fattoreorecircuito
Weight of total hours for rotation*
Defines the weight of the total operating hours of the individual
compressor in selecting which compressor to activate or deactivate,
within the individual “compressor module”.
num 2
144/CMP fattorespunticircuit
Weight of total starts for rotation
Defines the weight of the total starts of the individual compressor in
selecting which compressor to activate or deactivate, within the
individual “compressor module”.
num 2
146/CMP Potc1
Capacity compressor 1*
num 1
147/CMP Potc2
Capacity compressor 2*
num 1
148/CMP Potc3
Capacity compressor 3*
num 1
164/CMP comptype0
Type of compressor 1*
1
165/CMP comptype1
Type of compressor 2*
1
166/CMP comptype2
Type of compressor 3*
1
179/CMP AI1enable
Enable condensing temperature probe*
Defines the presence or absence of the probe
1
180/CMP AI2enable
Enable recovery temperature probe*
Defines the presence or absence of the probe
°C 1
181/CMP AI3enable
Enable condensing pressure transducer*
Defines the presence or absence of the transducer
°C 1
182/CMP AI4enable
Enable evaporation pressure transducer*
Defines the presence or absence of the transducer
Bar 1
183/CMP offsetprobe0
Condensing temperature correction offset*
Used to correct any reading errors
Bar 1
184/CMP offsetprobe1
Recovery temperature correction offset*
Used to correct any reading errors
2
185/CMP offsetprobe2
Condensing pressure correction offset*
Used to correct any reading errors
num 1
186/CMP offsetprobe3
Evaporation pressure correction offset*
Used to correct any reading errors
num 1
187/CMP Presenzarecupero
Enable recovery in the circuit*
Defines whether the circuit represented by the compressor module
includes a heat recovery exchanger and whether this is used.
num 1
232/CMP ore_compon1
Total hours compressor 1*
num 1
234/CMP ore_compon2
Total hours compressor 2*
num 1
236/CMP ore_compon3
Total hours compressor 3*
num 1
238/CMP Spunti1
Total starts compressor 1*
num 1
240/CMP Spunti2
Total starts compressor 2*
242/CMP Spunti3
Total starts compressor 3*
244/CMP OreCircuito
Total hours in the circuit*
267/CMP DeltaPreHPR
Differential to reset recovery pre-alarm*
268/CMP NPreHPRHour
Max number recovery HP pre-alarms per hour*
269/CMP SetPreHPR
Recovery high pressure pre-alarm set point*
270/CMP RitardoPreHPR
Delay to reset the recovery pre-alarm condition*
271/CMP BPFlussoStart
Recovery flow bypass*
NOTE: The parameters marked with the * are displayed (and must be set) for each of the compressor
modules present on the unit.