Data creazione 10/09/03 DS03I009GB--00 Pagina 29 di 59
Configuration Multi
Evap
Add Code Description UOM Pass
246/EVA OrePompa1
Total hours pump 1*
num 1
247/EVA NPump
Number of pumps present*
Defines the number of pumps present on the single evaporator module
num 2
249/EVA OrePompa2
Total hours pump 2*
num 1
250/EVA DoubleprobeEn
Enable double water outlet probe*
Defines the number of water outlet temperature probes present on the
single evaporator module.
2
252/EVA IstResist
Antifreeze heater deactivation hysteresis*
Refers to components located on the evaporator modules
°C 1
253/EVA SecondPumpEn
Enable second pump*
Refers to components located on the evaporator modules
2
254/EVA OffsetTin
Water inlet probe correction offset*
Refers to components located on the evaporator modules
°C 1
255/EVA MainPumpEn
Enable pump as main system pump*
Refers to components located on the evaporator modules
2
256/EVA OffsetTout1
Water outlet probe 1 correction offset*
Refers to components located on the evaporator modules
°C 1
257/EVA ResistEn
Enable antifreeze heaters*
Refers to components located on the evaporator modules
2
258/EVA OffsetTout2
Water outlet probe 2 correction offset*
Refers to components located on the evaporator modules
°C 1
259/EVA IngConf
Configure the type of analogue input*
Refers to components located on the evaporator modules
2
260/EVA ProbInEvap
Enable water inlet probe*
Refers to components located on the evaporator modules
2
NOTE: The parameters marked with the * are displayed (and must be set) for each of the compressor
modules present on the unit.