Data creazione 10/09/03 DS03I009GB--00 Pagina 30 di 59
Configuration Pumps
Add Code Description UOM Pass
68/CEN MainPumpEn
Enable main pump on central
Refers to components connected to the central module
1
69/CEN NPumps
Number of pumps on central
Refers to components connected to the central module
num 1
122/CEN OrePompa1
Total hours pump 1 central
Refers to components connected to the central module
num 1
123/CEN OrePompa2
Total hours pump 2 central
Refers to components connected to the central module
num 1
124/CEN RitCompressori
Time delay between start pumps and start compressors
Refers to components connected to the central module
Sec 1
125/CEN ByPassFlusso
Flow alarm time bypass from start pump
Refers to components connected to the central module
Sec 1
126/CEN RitPompaOFF
Stop pump delay from unit OFF
Refers to components connected to the central module
Sec 1
Configuration Probes
Add Code Description UOM Pass
9/CEN ProbeText
Enable outside temperature probe
1
23/CEN ProbeURExt
Enable outside RH% probe
1
65/CEN ProbeInEN
Enable water inlet probe on central
2
66/CEN ProbeOutEN
Enable water outlet probe on central
2
70/CEN ToutEn
Configure the use of the central module outlet temperature probe
The probe may be display only, or a control probe
2
76/CEN OffsetText
Outside temperature probe correction offset
°C 1
77/CEN OffsetTout
Water outlet temperature probe correction offset
°C 1
78/CEN OffsetTin
Water inlet temperature probe correction offset
°C 1
79/CEN OffsetWR
Water reset signal correction offset
1
80/CEN OffsetDL
Demand Limit signal correction offset
1
81/CEN OffsetURExt
Outside RH% probe correction offset
% 1
82/CEN TypeDL
Configure type of Demand Limit signal
1
83/CEN TypeWR
Configure type of Water reset signal
1