Controls
Outside temp.Compens.
Add Code Description UOM Pass
1/CEN EnCompExt Enable external compensation
Used to enable or disable the function
1
4/CEN MaxCExtC Maximum external compensation value in cooling
Maximum value than can be added to the “Current Set point” in
conditions of minimum outside temperature
°C 1
5/CEN MaxCExtH Maximum external compensation value in heating
“Current Set point” Maximum correction value in conditions of
maximum outside temperature
°C 1
93/CEN CextMaxH Outside temperature for maximum compensation in heating
Outside temperature (value higher than the value set for parameter 98)
that determines the maximum set point compensation.
°C 1
94/CEN CextMinH Outside temperature for minimum compensation in heating
Outside temperature at which the unit works with the maximum set
point.
°C 1
106/CEN CextMaxC Outside temperature for maximum compensation in cooling
Outside temperature (value less than the value set for parameter 111)
that determines the maximum set point compensation.
°C 1
107/CEN CextMinC Outside temperature for minimum compensation in cooling
Outside temperature at which the unit works with the minimum set
point.
°C 1
110/CEN HexMinC Outside enthalpy for minimum compensation
Outside enthalpy (higher than the value set for parameter 115) that
determines the minimum set point.
h 1
111/CEN HexMaxC Outside enthalpy for maximum compensation
Outside enthalpy (less than the value set for parameter 114) that
determines the maximum set point (maximum compensation)
h 1
Controls Demand Limit
Add Code Description UOM Pass
7/CEN DemandLimitEn Enable Demand Limit
Enable or disable the function
1
128/CEN Treaction Demand limit reaction time
Filter used to account for excessively fast variations of the input signal
Sec 1