Data creazione 10/09/03 DS03I009GB--00 Pagina 35 di 59
Controls
Time compens
Add Code Description UOM Pass
16 CompONEN Enable running time compensation
Enables the compensation function on the compressor running time
1
99 TimeOnMax Upper running time compensation time
Compressor operating time considered sufficient.
Sec 1
100 TimeOnMin Lower running time compensation time
Compressor operating time considered too short.
Sec 1
133 MaxCON Maximum running time compensation value
Maximum offset to add to the “current step difference”.
NB: The value entered will be added three consecutive times if the
running time remains below the value set for parameter 100; entering
the value 1.5, for example, will bring about a maximum compensation
of 4.5°C
°C 1
Controls
Duty cycle compens
Add Code Description UOM Pass
13/CEN MaxCompDuty Maximum duty cycle compensation value
Maximum value that can be added to the “current step difference” in
conditions of maximum compensation
°C 1
14/CEN CompDutyEn Enable duty cycle compensation
Used to enable or disable the function
1
16/CEN DutyVar Critical value of the duty cycle num 1
97/CEN TimeCycle Time base for calculating the duty cycle Sec 1