EasyManuals Logo

CLIVET TALK User Manual

CLIVET TALK
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
Data creazione 10/09/03 DS03I009GB--00 Pagina 35 di 59
Controls
Time compens
Add Code Description UOM Pass
16 CompONEN Enable running time compensation
Enables the compensation function on the compressor running time
1
99 TimeOnMax Upper running time compensation time
Compressor operating time considered sufficient.
Sec 1
100 TimeOnMin Lower running time compensation time
Compressor operating time considered too short.
Sec 1
133 MaxCON Maximum running time compensation value
Maximum offset to add to the “current step difference”.
NB: The value entered will be added three consecutive times if the
running time remains below the value set for parameter 100; entering
the value 1.5, for example, will bring about a maximum compensation
of 4.5°C
°C 1
Controls
Duty cycle compens
Add Code Description UOM Pass
13/CEN MaxCompDuty Maximum duty cycle compensation value
Maximum value that can be added to the “current step difference” in
conditions of maximum compensation
°C 1
14/CEN CompDutyEn Enable duty cycle compensation
Used to enable or disable the function
1
16/CEN DutyVar Critical value of the duty cycle num 1
97/CEN TimeCycle Time base for calculating the duty cycle Sec 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET TALK and is the answer not in the manual?

CLIVET TALK Specifications

General IconGeneral
BrandCLIVET
ModelTALK
CategoryController
LanguageEnglish

Related product manuals