Data creazione 10/09/03 DS03I009GB--00 Pagina 34 di 59
Controls
Antifrost
CENTRAL MODULE ANTIFREEZE MANAGEMENT PARAMETERS
Add Code Description UOM Pass
21/CEN IsPreAF Antifreeze pre-alarm hysteresis °C 1
22/CEN IstAllFreeze Antifreeze alarm hysteresis °C 1
92/CEN ByPassFreeze Antifreeze alarm bypass time
Antifreeze alarm bypass time from the activation in heat pump mode.
With the unit in standby and an alarm active, heating operation can be
activated by bypassing the alarm for the time indicated.
Sec 1
98/CEN ScanPreAF Antifreeze pre-alarm scan time Sec 1
112/CEN MinFreeze Minimum antifreeze value °C 1
113/CEN MaxFreeze
Maximum antifreeze value
°C 1
115/CEN AllFreeze
Antifreeze alarm set point
°C 0
121/CEN PreAF
Antifreeze pre-alarm set point
°C 0
261/CEN SetResist
Antifreeze heater set point
°C
262/CEN IstResist
Antifreeze heater hysteresis
°C
264/CEN ResistEn
Enable antifreeze heaters
Num
Controls
Capacity compens
Add Code Description UOM Pass
0/CEN ENCCar Enable load compensation 1
2/CEN CompCarH Maximum load compensation value in heating
Limit of the temperature offset added to the “Current Step Difference”
in minimum load conditions.
°C 1
3/CEN CompCarC Maximum load compensation value in cooling
Limit of the temperature offset added to the “Current Step Difference”
in minimum load conditions.
°C 1
10/CEN MinDeltaC Minimum T diff. in cooling
Temperature difference between water inlet and outlet, corresponding
to maximum compensation
°C 1
28/CEN MaxDeltaH Maximum T diff. in heating
Temperature difference between the water inlet and outlet,
corresponding to minimum compensation
°C 1
29/CEN MinDeltaH Minimum T diff. in heating
Temperature difference between water inlet and outlet, corresponding
to maximum compensation
°C 1
30/CEN MaxDeltaC Maximum T diff. in cooling
Temperature difference between water inlet and outlet, corresponding
to maximum compensation
°C 1
101/CEN MediaDelta Time base for the average on the T diff.
The system calculates the average of the T diff. between the water inlet
and outlet based on the samples measured in the time indicated.
Sec 1