Compact controller ER 2022S and ER 2022SA
8. Configuration
8.1 Analog inputs ”Inp”
Analog input 1 InP1 →
offset
The measurement offset is used to correct a measured
value by a certain amount upwards or downwards.
Examples:
Measured
Displayed
value offset
value
294.7 +0.3 295.0
295.3 - 0.3 295.0
Special cas:2-wire circuit
If the input is connected to a resistance thermometer in
2-wire circuit, then the lead resistance is set in ohms
On transducers with standard signal and on
potentiometers, a display value is assigned to the
physical signal.
Example: 0 — 20mA
�
0 — 1500°C.
The range of the physical signal can be 20 % wider or
narrower without generating an out-of-range signal.
constant
To adjust the digital input filter (0sec = filter off).
63% of the alterations are acquired after 2x filter time
constant at a signal step change.
When the filter time constant is large:
-
high damping of disturbance signals
-
slow reaction of the process value
display to process value changes.
low limit-frequency (2nd order low-pass filter)
see description on the following pages.
end value
current
monitoring
(output)
1…10
Output 1—10
The heater current is measured via a current transformer
with standard signal output and can be monitored by
linking analog output 2 to a limit comparator.
The input signal range is 0 — 50mA AC (see probe type:
“Heater current”) and must be scaled correspondingly
(display start/end).
The heater current is measured when the heating contact
correcting
Resistance at 25°C/77°F for linearization “KTY 11-6”
NOTE: Factory settings shown with BOLD text